[RQ8.3] The flags of the SafetyProvider (ResponseSPDU.Flags) shall be used as shown in Table 19.
Table 19 – Structure of ResponseSPDU.Flags
Bit nr. |
Name |
Description |
LSB = Bit 0 |
Operator acknowledgment at the provider, hereby forwarded to the SafetyConsumer, see OperatorAckProvider in the SAPI of the SafetyProvider, Clause 7.3.1. |
|
Bit 1 |
Activation of fail-safe values by the safety application at the SafetyProvider, hereby forwarded to the SafetyConsumer, see ActivateFSV in the SAPI of the SafetyProvider, Clause 7.3.1. |
|
Bit 2 |
Enabling and disabling of test mode in the SafetyProvider, hereby forwarded to the SafetyConsumer, see EnableTestMode in the SAPI of the SafetyProvider, Clause 7.3.1. |
|
Bit 3 ...... 7 |
Reserved for future use |
Always set to zero, not evaluated. |
[RQ8.4] Flags reserved for future use shall be set to zero by the SafetyProvider and shall not be evaluated by the SafetyConsumer.