8.1.1.5 ResponseSPDU: Flags

[RQ8.3] The flags of the SafetyProvider (ResponseSPDU.Flags) shall be used as shown in Table 19.

Table 19 – Structure of ResponseSPDU.Flags 

Bit nr.

Name

Description

LSB =

Bit 0

OperatorAckProvider

Operator acknowledgment at the provider, hereby forwarded to the SafetyConsumer, see OperatorAckProvider in the SAPI of the SafetyProvider, Clause 7.3.1.

Bit 1

ActivateFSV

Activation of fail-safe values by the safety application at the SafetyProvider, hereby forwarded to the SafetyConsumer, see ActivateFSV in the SAPI of the SafetyProvider, Clause 7.3.1.

Bit 2

TestModeActivated

Enabling and disabling of test mode in the SafetyProvider, hereby forwarded to the SafetyConsumer, see EnableTestMode in the SAPI of the SafetyProvider, Clause 7.3.1.

Bit 3 ...... 7

Reserved for future use

Always set to zero, not evaluated.

[RQ8.4] Flags reserved for future use shall be set to zero by the SafetyProvider and shall not be evaluated by the SafetyConsumer.