The SupervisionProcessFluidType provides Variables used for monitoring the Pump process fluid. It is formally defined in Table 37. For the generation of events, the SupervisionProcessFluidType has references to the four Namur NE 107 statuses defined in OPC 10000-100. The InputNode Property of the Alarm shall contain the NodeId of the Component.
Table 37 – SupervisionProcessFluidType Definition
Attribute |
Value |
|||||
BrowseName |
SupervisionProcessFluidType |
|||||
IsAbstract |
False |
|||||
References |
Node Class |
BrowseName |
DataType |
TypeDefinition |
Other |
|
Subtype of the 2:FunctionalGroupType defined in OPC 10000-100, i.e. inheriting the InstanceDeclarations of that Node. |
||||||
0:HasComponent |
Variable |
Blockage |
0:Boolean |
0:TwoStateDiscreteType |
O, RO |
|
0:HasComponent |
Variable |
Cavitation |
0:Boolean |
0:TwoStateDiscreteType |
O, RO |
|
0:HasComponent |
Variable |
Condensation |
0:Boolean |
0:TwoStateDiscreteType |
O, RO |
|
0:HasComponent |
Variable |
Dry |
0:Boolean |
0:TwoStateDiscreteType |
O, RO |
|
0:HasComponent |
Variable |
Flow |
0:Boolean |
0:TwoStateDiscreteType |
O, RO |
|
0:HasComponent |
Variable |
Gas |
0:Boolean |
0:TwoStateDiscreteType |
O, RO |
|
0:HasComponent |
Variable |
Liquid |
0:Boolean |
0:TwoStateDiscreteType |
O, RO |
|
0:HasComponent |
Variable |
Pressure |
0:Boolean |
0:TwoStateDiscreteType |
O, RO |
|
0:HasComponent |
Variable |
ProcessFault |
0:Boolean |
0:TwoStateDiscreteType |
O, RO |
|
0:HasComponent |
Variable |
Solid |
0:Boolean |
0:TwoStateDiscreteType |
O, RO |
|
0:HasComponent |
Variable |
Stall |
0:Boolean |
0:TwoStateDiscreteType |
O, RO |
|
0:HasComponent |
Variable |
Temperature |
0:Boolean |
0:TwoStateDiscreteType |
O, RO |
|
0:HasComponent |
Variable |
Viscosity |
0:Boolean |
0:TwoStateDiscreteType |
O, RO |
|
0:GeneratesEvent |
ObjectType |
2:CheckFunctionAlarmType |
Defined in OPC 10000-100 |
|||
0:GeneratesEvent |
ObjectType |
2:FailureAlarmType |
Defined in OPC 10000-100 |
|||
0:GeneratesEvent |
ObjectType |
2:MaintenanceRequiredAlarmType |
Defined in OPC 10000-100 |
|||
0:GeneratesEvent |
ObjectType |
2:OffSpecAlarmType |
Defined in OPC 10000-100 |
The InstanceDeclarations of the SupervisionProcessFluidType have additional Attributes defined in Table 38. The Variables and the associated Descriptions are based on the standard VDMA 24223-1.
Table 38 – SupervisionProcessFluidType Attribute values for child Nodes
BrowsePath |
Description Attribute |
Blockage |
This attribute indicates a closed valve operation. |
Cavitation |
This attribute indicates cavitation of the pump liquid. |
Condensation |
This attribute indicates abnormal condensation in flow medium. |
Dry |
This attribute indicates a dry running. |
Flow |
This attribute indicates an abnormal flow of the pump fluid. |
Gas |
This attribute indicates a significant amount of gas in the pump liquid. |
Liquid |
This attribute indicates a significant amount of liquid in the flow medium. |
Pressure |
This attribute indicates an abnormal pressure of the pump fluid. |
ProcessFault |
This attribute indicates a generic process problem. |
Solid |
This attribute indicates an significant amount of solid in the pump fluid. |
Stall |
This attribute indicates a stall of the pump liquid. |
Temperature |
This attribute indicates an abnormal temperature of the pump fluid. |