LineFilterPowerLoss contains the power loss for a 50 Hz line operated with rated current/power. The unit shall be watt [W].
LineFilterEmcCategory refers to the installation of the filter in one of the equipment categories specified by the IEC/EN 61800-3. The values of the MultiStateValueDiscreteType variable are defined in Table 106 and shall be used. Additional values will be added in the specification. Manufacturer-specific extensions are not foreseen.
Table 106 – PtInputFilterAttributesType Attribute values for child Nodes
BrowsePath |
Value Attribute |
Description Attribute |
||
|
[ { "Value": 0, "DisplayName": "OTHER", "Description": "Other" }, { "Value": 1, "DisplayName": "CATEGORY_C1", "Description": "Installed in an equipment of rated voltage less than 1000 V, intended for use in residential premises and establishments directly connected without intermediate transformers to a low-voltage power supply network which supplies buildings used for residential purposes" }, { "Value": 2, "DisplayName": "CATEGORY_C2", "Description": "Installed in an equipment of rated voltage less than 1000 V, which is neither a plug-in device nor a movable device and, when used as described for Category C1, is intended to be installed and commissioned only by a professional" }, { "Value": 3, "DisplayName": "CATEGORY_C3", "Description": "Installed in an equipment of rated voltage less than 1000 V, intended for use in establishments other than those directly connected to a low voltage power supply network which supplies buildings used for residential purposes" }, { "Value": 4, "DisplayName": "CATEGORY_C4", "Description": "Installed in an equipment of rated voltage equal to or above 1000 V, or rated current equal to or above 400 A, or intended for use in complex systems (in Industrial areas or technical areas of any building)" } ] |
|
||
|
[ { "Value": 0, "DisplayName": "CLASS_A", "Description": "Installed in an equipment suitable for use in all locations other than those allocated in residential environments and those directly connected to a low voltage power supply network which supplies buildings used for domestic purposes" }, { "Value": 1, "DisplayName": "CLASS_B", "Description": "Installed in an equipment suitable for use in locations in residential environments and in establishments directly connected to a low voltage power supply network which supplies buildings used for domestic purposes" } ] |
|
||
|
[ { "Value": 0, "DisplayName": "OTHER", "Description": "Other group" }, { "Value": 1, "DisplayName": "GROUP_1", "Description": "Installed in an equipment which is not covered by the one referred to in group 2" }, { "Value": 2, "DisplayName": "GROUP_2", "Description": "Installed in an equipment in which radio-frequency energy in the frequency range 9 kHz to 400 GHz is intentionally generated and used or only used locally, in the form of electromagnetic radiation, inductive and/or capacitive coupling, for the treatment of material, for inspection/analysis purposes, or for transfer of electromagnetic energy" } ] |
|
LineFilterEmcClass refers to the installation of the filter in one of the equipment classes specified by the EN 55011. The values of the MultiStateValueDiscreteType variable are defined in Table 106 and shall be used. Additional values will be added in the specification. Manufacturer-specific extensions are not foreseen.
LineFilterEmcGroup refers to the installation of the filter in one of the equipment groups specified by the EN 55011. The values of the MultiStateValueDiscreteType variable are defined in Table 106 and shall be used. Additional values will be added in the specification. Manufacturer-specific extensions are not foreseen.