The PtAnalogOutputElectricalAttributesType provides analog output asset attributes and is formally defined in Table 132.
Table 132 – PtAnalogOutputElectricalAttributesType Definition
Attribute |
Value |
||||
BrowseName |
PtAnalogOutputElectricalAttributesType |
||||
IsAbstract |
False |
||||
References |
Node Class |
BrowseName |
DataType |
TypeDefinition |
Other |
Subtype of the PtCommonAssetAttributesType defined in chapter 7.11 |
|||||
0:HasComponent |
Variable |
AnalogOutputElectricalType |
0:UInt16 |
0:MultiStateValueDiscreteType |
O, RO |
0:HasProperty |
Variable |
NumberOfChannels |
0:UInt16 |
0:PropertyType |
O, RO |
0:HasComponent |
Variable |
LoadResistance |
0:Float |
0:AnalogUnitType |
O, RO |
0:HasComponent |
Variable |
FrequencyRange |
0:Range |
0:BaseDataVariableType |
O, RO |
Conformance Units |
|||||
Powertrain Attributes Information |
AnalogOutputElectricalType provides the used analog output(s). The values of the MultiStateValueDiscreteType variable are defined in Table 133 and shall be used. The values 0-199 are reserved for future extensions of this specification. The values 200-299 shall be used for vendor-specific extensions of this variable.
Table 133 – PtAnalogOutputElectricalAttributesType Attribute values for child Nodes
BrowsePath |
Value Attribute |
Description Attribute |
||
|
[ { "Value": 0, "DisplayName": "VOLTAGE_0-10V", "Description": "Voltage range 0-10 volt" }, { "Value": 1, "DisplayName": "VOLTAGE_-10-10V", "Description": "Voltage range -10-10 volt" }, { "Value": 2, "DisplayName": "CURRENT_0-20MA", "Description": "Current range 0-20 milliampere" }, { "Value": 3, "DisplayName": "CURRENT_4-20MA", "Description": "Current range 4-20 milliampere" }, { "Value": 4, "DisplayName": "TEMPERATURE_PT1000", "Description": "PT1000 temperature sensor" }, { "Value": 5, "DisplayName": "TEMPERATURE_PT100", "Description": "PT100 temperature sensor" }, { "Value": 6, "DisplayName": "TEMPERATURE_KTY", "Description": "KTY temperature sensor" }, { "Value": 7, "DisplayName": "TEMPERATURE_KTY84", "Description": "KTY84 temperature sensor" }, { "Value": 8, "DisplayName": "TEMPERATURE_PTC", "Description": "PTC temperature sensor" }, { "Value": 9, "DisplayName": "VOLTAGE", "Description": "Other voltage interface" }, { "Value": 10, "DisplayName": "CURRENT", "Description": "Other current interface" }, { "Value": 11, "DisplayName": "TEMPERATURE", "Description": "Other temperature interface" }, { "Value": 12, "DisplayName": "CONFIGURABLE", "Description": "Configurable" } ] |
|
NumberOfChannels provides the number of channels of the analog output representation.
LoadResistance provides the minimum value of the load resistance. The unit shall be ohm [Ω].
FrequencyRange provides the range of frequencies usable for the analog output. The unit shall be hertz [Hz].
The attributes of the PtAnalogOutputElectricalAttributesType have additional subattributes which are defined in Table 134.
Table 134 – PtAnalogOutputElectricalAttributesType additional subattributes
BrowsePath |
References |
NodeClass |
BrowseName |
DataType |
TypeDefinition |
Others |
FrequencyRange |
0:HasProperty |
Variable |
0:EngineeringUnits |
EUInformation |
0:PropertyType |
M |