This OPC UA ObjectType is used representing the basic specification of a TCD temperature control device with its subcomponents. It is formally defined in Table 2.
Table 2 – TCDSpecificationType Definition
| 
 Attribute  | 
        
 Value  | 
||||
| 
 BrowseName  | 
        
 TCDSpecificationType  | 
||||
| 
 IsAbstract  | 
        
 False  | 
||||
| 
 References  | 
        
 Node Class  | 
        
 BrowseName  | 
        
 DataType  | 
        
 TypeDefinition  | 
        
 Other  | 
| 
 Subtype of 0:BaseObjectType defined in OPC UA Part 5  | 
|||||
| 
 0:HasComponent  | 
        
 Variable  | 
        
 MaxTemperature  | 
        
 0:Int32  | 
        
 0:AnalogItemType  | 
        
 M, RO  | 
| 
 0:HasComponent  | 
        
 Variable  | 
        
 PowerValue  | 
        
 0:Double  | 
        
 0:AnalogItemType  | 
        
 M, RO  | 
| 
 0:HasComponent  | 
        
 Variable  | 
        
 ConnectedLoad  | 
        
 0:Double  | 
        
 0:AnalogItemType  | 
        
 M, RO  | 
| 
 0:HasComponent  | 
        
 Variable  | 
        
 NominalFlowRate  | 
        
 0:Double  | 
        
 0:AnalogItemType  | 
        
 M, RO  | 
| 
 0:HasComponent  | 
        
 Variable  | 
        
 CoolingCapacity  | 
        
 0:UInt32  | 
        
 0:AnalogItemType  | 
        
 O, RO  | 
| 
 0:HasProperty  | 
        
 Variable  | 
        
 DeviceZoneId  | 
        
 0:String  | 
        
 0:PropertyType  | 
        
 O, RO  | 
Description:Defines the maximum working temperature of the TCD
Unit: °C or °F
Example:160
Description:Power value, defines the heating capacity of the TCD with the rated voltage
Unit: kW
Example: 8
Description:Connected load, defines the connections of the TCD (pump performance, heating capacity and performance of the remaining components)
Unit: kW
Example: 10.2
Description:Nominal flow rate, defines the maximum achievable flow rate of the TCD
Unit: l/min, gal/min or ft³/min
Example: 45
Description:Power value for cooling, defines the power value for cooling at temperature difference 60 K between cooling water and heat transfer medium
Unit: kW
Example:30
Description:As written in 4.1, for a TCD with several device zones, there shall be several instances of TCD_InterfaceType with one object DeviceZone each. In this case, the DeviceZoneId shall be used to identify the different device zones.
Example:“A”