5.3.2.6.3 Asset installed

The user wants to be informed if assets in the plant or machine were added. The following table describes criteria to detect changes.

Implements AM5.

Table 12 – Criteria for added assets

Added asset

Criteria

PROFINET Service

Device

Device with unknown MAC address in the network

DCP-Identify-All

ModuleSubmodule

Real configuration contains a new module/submodule

RecordRead RealIdentificationData for all API’s

Asset

Asset list contains a new entry

RecordRead AM_Info