This Method sets the Value of the ManualProcessValue Variable. The security constraints defined in chapter 6.7 apply.

Signature

SetManualProcessValue (

[in] RioAnalogDataType ManualProcessValue

);

Argument

Description

ManualProcessValue

Desired Value of the ManualProcessValue Variable.

The Method Result Codes (defined in Call Service) are defined in Table 34.

Table 34 – Possible Method result codes

Result Code

Description

Good

The Method execution was successful.

Bad_UserAccessDenied

The user has not the right to execute the Method.

Bad_InvalidArgument

The Server is not able to apply the argument value. For instance, the Server might reject manual values not within the channels value bounds.

Bad_UnexpectedError

The Server is not able to execute the function because an unexpected error occurred. The Device might be temporarily unavailable or unreachable due to network failure.

If the ManualProcessValue Variable has already the same Value as the argument, the Method shall do nothing and return Good as result code.