The following table is based on Table 26 Energy measurements in the PROFIenergy specification.
PE MeasurementID |
Measurements |
Unit |
DataType |
Phase |
PNEMMapping |
200 |
Active Energy Import |
Wh |
Float32 |
total |
AcActiveEnergyTotalImportLp |
201 |
Active Energy Export |
Wh |
Float32 |
total |
AcActiveEnergyTotalExportLp |
202 |
Reactive Energy Import |
varh |
Float32 |
total |
AcReactiveEnergyTotalImporttLp |
203 |
Reactive Energy Export |
varh |
Float32 |
total |
AcReactiveEnergyTotalExportLp |
204 |
Apparent Energy |
VAh |
Float32 |
total |
|
205 |
Active Energy Sum |
Wh |
Float32 |
total |
|
206 |
Reactive Energy Sum |
Wh |
Float32 |
total |
|
… |
|
|
|
|
|
210 |
Active Energy Import |
Wh |
Float64 |
total |
AcActiveEnergyTotalImportHp |
211 |
Active Energy Export |
Wh |
Float64 |
total |
AcActiveEnergyTotalExportHp |
212 |
Reactive Energy Import |
varh |
Float64 |
total |
AcReactiveEnergyTotalImporttHp |
213 |
Reactive Energy Export |
varh |
Float64 |
total |
AcReactiveEnergyTotalExportHp |
214 |
Apparent Energy |
VAh |
Float64 |
total |
|
215 |
Active Energy Sum |
Wh |
Float64 |
total |
|
216 |
Reactive Energy Sum |
Wh |
Float64 |
total |
|