This chapter defines the corresponding Conformance Units for the OPC UA Information Model for PE Energy Management.
Table 61 – Conformance Units for PE Energy Management
Category |
Title |
Description |
Server |
PNEM Standby Management |
Supports the Standby Management functionality defined in Standby Management Information Model. |
Server |
PNEM Standby Management Control |
Supports the Standby Management functionality defined in Standby Management Information Model. The Methods StartPause, EndPause, PauseTime are supported. |
Server |
PNEM Energy Measurement |
Supports the Energy Measurement functionality defined in Energy Measurement Information Model. |
Server |
PNEM Sleep Mode WOL |
Supports the Sleep Mode WOL functionality defined in Sleep Mode WOL Functionality Information Model. |
Server |
PNEM Energy Management Support |
Supports at least one of the Conformance Units: PNEM Standby Management, PNEM Energy Measurement or PNEM Power Off. |
Server |
PNEM PROFIenergy |
Supports the PeServiceAccessPointType ObjectType defined in PE Energy Management Information Model (The device implements the PROFIenergy Common Application Profile). |
Server |
PNEM EnergyProfile E0 |
IEnergyProfileE0 Interface is supported by EnergyMeasurementType Object instances. |
Server |
PNEM EnergyProfile E1 |
IEnergyProfileE1 Interface is supported by EnergyMeasurementType Object instances. |
Server |
PNEM EnergyProfile E2 |
IEnergyProfileE2 Interface is supported by EnergyMeasurementType Object instances. |
Server |
PNEM EnergyProfile E3 |
IEnergyProfileE3 Interface is supported by EnergyMeasurementType Object instances. |
Server |
PNEM EnergyProfile D0 |
IEnergyProfileD0 Interface is supported by EnergyMeasurementType Object instances. |
Table 62 lists all Profiles defined in this document and defines their URIs.
Table 62 – Profile URIs for PE Energy Management
Profile |
URI |
PNEM Energy Management Server Profile |
http://opcfoundation.org/UA-Profile/PNEM/Server/EnergyManagement |
PNEM PROFINET Energy Management Server Profile |
http://opcfoundation.org/UA-Profile/PNEM/Server/PROFINETEnergyManagement |
PNEM Energy Management Control Server Profile |
http://opcfoundation.org/UA-Profile/PNEM/Server/EnergyManagementControl |
PNEM PROFINET Energy Management Control Server Profile |
http://opcfoundation.org/UA-Profile/PNEM/Server/PROFINETEnergyManagementControl |
PNEM Energy Controller Server Facet |
http://opcfoundation.org/UA-Profile/PNEM/Server/EnergyController |
The following sections specify the Facets available for Servers that implement the PE Energy Management companion specification. Each section defines and describes a Facet or Profile.
Table 63 – PNEM Energy Management Server Profile
Group |
Conformance Unit / Profile Title |
M / O |
PNEM |
PNEM Standby Management |
O |
PNEM |
PNEM Energy Measurement |
O |
PNEM |
PNEM Sleep Mode WOL |
O |
PNEM |
PNEM EnergyProfile E0 |
O |
PNEM |
PNEM EnergyProfile E1 |
O |
PNEM |
PNEM EnergyProfile E2 |
O |
PNEM |
PNEM EnergyProfile E3 |
O |
PNEM |
PNEM EnergyProfile D0 |
O |
PNEM |
PNEM Energy Management Support |
M |
Profile |
0:Nano Embedded Device 2017 Server Profilehttp://opcfoundation.org/UA-Profile/Server/NanoEmbeddedDevice2017 |
M |
Profile |
0:Data Access Server Facethttp://opcfoundation.org/UA-Profile/Server/DataAccess |
M |
Profile |
0:ComplexType 2017 Server Facethttp://opcfoundation.org/UA-Profile/Server/ComplexTypes2017 |
M |
Subscription Services |
0:SubscriptionDurablehttp://opcfoundation.org/UA-Profile/Server/DurableSubscription |
M |
Table 64 – PNEM Energy Management Control Server Profile
Group |
Conformance Unit / Profile Title |
M / O |
Profile |
PNEM Energy Controller Server Facet |
M |
Profile |
PNEM Energy Management Server Profile |
M |
Profile |
0:Embedded Device 2017 Server Profilehttp://opcfoundation.org/UA-Profile/Server/EmbeddedUA2017 |
M |
Table 65 – PNEM Energy PROFINET Management Server Profile
Group |
Conformance Unit / Profile Title |
M / O |
PNEM |
PNEM PROFIenergy |
M |
Profile |
PNEM Energy Management Server Profile |
M |
Table 66 – PNEM PROFINET Energy Management Control Server Profile
Group |
Conformance Unit / Profile Title |
M / O |
Profile |
PNEM PROFIenergy |
M |
Profile |
PNEM Energy Management Control Server Profile |
M |
Table 67 – PNEM Energy Controller Server Facet
Group |
Conformance Unit / Profile Title |
M / O |
PNEM |
PNEM Standby Management Control |
M |
Profile |
2:Locking_Server_Facet |
M |
This specification does not define any Client Facets.