The MaintenanceRequestedConditionType is sent when the manufacturer wants to inform the operator that the system requires maintenance. The condition is also sent when the maintenance is no longer required. It is formally defined in Table 83.
Table 83 – MaintenanceRequestedConditionType Definition
Attribute |
Value |
||||
BrowseName |
MaintenanceRequestedConditionType |
||||
IsAbstract |
False |
||||
References |
Node Class |
BrowseName |
DataType |
TypeDefinition |
Other |
Subtype of the AcknowledgeableConditionType defined in OPC 10000-9 |
|||||
0:HasProperty |
Variable |
Requested |
0:Boolean |
0:PropertyType |
M,R |
Conformance Units |
|||||
|
The property Requested reflects the value of the MaintenanceRequested property of the object from which the event originates at the time the event was sent.
The MaintenanceSwitchConditionType is sent when the physical maintenance switch is toggled. It is formally defined in Table 84.
Table 84 – MaintenanceSwitchConditionType Definition
Attribute |
Value |
||||
BrowseName |
MaintenanceSwitchConditionType |
||||
IsAbstract |
False |
||||
References |
Node Class |
BrowseName |
DataType |
TypeDefinition |
Other |
Subtype of the ConditionType defined in OPC 10000-9 |
|||||
0:HasProperty |
Variable |
SwitchOn |
0:Boolean |
0:PropertyType |
M,R |
Conformance Units |
|||||
|
The property SwitchOn reflects the value of the MaintenanceSwitchOn property of the object from which the event originates at the time the event was sent.
The MalfunctionAlarmType is sent when the component has an error that may prevent it from operating. The type of the error depends on the specific component that emits the alarm. This specification does not specify the details of the error in a standardized way. It is formally defined in Table 85.
Table 85 – MalfunctionAlarmType Definition
Attribute |
Value |
||||
BrowseName |
MalfunctionAlarmType |
||||
IsAbstract |
False |
||||
References |
Node Class |
BrowseName |
DataType |
TypeDefinition |
Other |
Subtype of the OffNormalAlarmType defined in OPC 10000-9 |
|||||
Conformance Units |
|||||
|
The DischargeSystemType sends an event of type DischargeContainerInstalledConditionType when the container is installed or removed. It is formally defined in Table 86.
Table 86 – DischargeContainerInstalledConditionType Definition
Attribute |
Value |
||||
BrowseName |
DischargeContainerInstalledConditionType |
||||
IsAbstract |
False |
||||
References |
Node Class |
BrowseName |
DataType |
TypeDefinition |
Other |
Subtype of the ConditionType defined in OPC 10000-9 |
|||||
0:HasProperty |
Variable |
Installed |
0:Boolean |
0:PropertyType |
M,R |
Conformance Units |
|||||
|
The property Installed reflects the value of the DischargeContainerInstalled property of the DischargeSystemType at the time the event was sent.
The WashingAgentInflowOpenConditionType is triggered when the washing agent inflow valve is opened or closed. It is formally defined in Table 87.
Table 87 – WashingAgentInflowOpenConditionType Definition
Attribute |
Value |
||||
BrowseName |
WashingAgentInflowOpenConditionType |
||||
IsAbstract |
False |
||||
References |
Node Class |
BrowseName |
DataType |
TypeDefinition |
Other |
Subtype of the ConditionType defined in OPC 10000-9 |
|||||
0:HasProperty |
Variable |
Open |
0:Boolean |
0:PropertyType |
M,R |
Conformance Units |
|||||
|
The property Open reflects the value of the WashingAgentInflowOpen property of the WetSeparatorType at the time the event was sent.
The WashingAgentInflowMalfunctionAlarmType event is triggered when an error occurs on the washing agent inflow. It is formally defined in Table 88.
Table 88 – WashingAgentInflowMalfunctionAlarmType Definition
Attribute |
Value |
||||
BrowseName |
WashingAgentInflowMalfunctionAlarmType |
||||
IsAbstract |
False |
||||
References |
Node Class |
BrowseName |
DataType |
TypeDefinition |
Other |
Subtype of the OffNormalAlarmType defined in OPC 10000-9 |
|||||
Conformance Units |
|||||
|
The WashingAgentDrainOpenConditionType is triggered when the washing agent drain valve is opened or closed. It is formally defined in Table 89.
Table 89 – WashingAgentDrainOpenConditionType Definition
Attribute |
Value |
||||
BrowseName |
WashingAgentDrainOpenConditionType |
||||
IsAbstract |
False |
||||
References |
Node Class |
BrowseName |
DataType |
TypeDefinition |
Other |
Subtype of the ConditionType defined in OPC 10000-9 |
|||||
0:HasProperty |
Variable |
Open |
0:Boolean |
0:PropertyType |
M,R |
Conformance Units |
|||||
|
The property Open reflects the value of the WashingAgentDrainOpen property of the WetSeparatorType at the time the event was sent.
The WashingAgentDrainMalfunctionAlarmType is triggered when an error occurs on the washing agent drain. It is formally defined in Table 90.
Table 90 – WashingAgentDrainMalfunctionAlarmType Definition
Attribute |
Value |
||||
BrowseName |
WashingAgentDrainMalfunctionAlarmType |
||||
IsAbstract |
False |
||||
References |
Node Class |
BrowseName |
DataType |
TypeDefinition |
Other |
Subtype of the OffNormalAlarmType defined in OPC 10000-9 |
|||||
Conformance Units |
|||||
|
The EndOfFilterRollAlarmType is triggered when the automatic roll filter reaches the end of the filter roll. It is formally defined in Table 91.
Table 91 – EndOfFilterRollAlarmType Definition
Attribute |
Value |
||||
BrowseName |
EndOfFilterRollAlarmType |
||||
IsAbstract |
False |
||||
References |
Node Class |
BrowseName |
DataType |
TypeDefinition |
Other |
Subtype of the OffNormalAlarmType defined in OPC 10000-9 |
|||||
Conformance Units |
|||||
|
The HighVoltageUnitSupplyActiveEventType is triggered when the high voltage unit supply is activated or deactivated. it is formally defined in Table 92.
Table 92 – HighVoltageUnitSupplyActiveEventType Definition
Attribute |
Value |
||||
BrowseName |
HighVoltageUnitSupplyActiveEventType |
||||
IsAbstract |
True |
||||
References |
Node Class |
BrowseName |
DataType |
TypeDefinition |
Other |
Subtype of the BaseEventType defined in OPC 10000-9 |
|||||
0:HasProperty |
Variable |
Active |
0:Boolean |
0:PropertyType |
M,R |
Conformance Units |
|||||
|
The property Active reflects the value of the SupplyActive property of the HighVoltageUnitType at the time the event was triggered.
The ContainerNotClosedConditionType is triggered when the filter aid reservoir is opened or closed. It is formally defined in Table 93.
Table 93 – ContainerOpenConditionType Definition
Attribute |
Value |
||||
BrowseName |
ContainerOpenConditionType |
||||
IsAbstract |
False |
||||
References |
Node Class |
BrowseName |
DataType |
TypeDefinition |
Other |
Subtype of the ConditionType defined in OPC 10000-9 |
|||||
0:HasProperty |
Variable |
Open |
0:Boolean |
0:PropertyType |
M,R |
Conformance Units |
|||||
|
The property Open reflects the value of the ContainerOpen property of the FilterAidDeviceType at the time the condition was triggered.
The CompressedAirSupplyInterruptedAlarmType is triggered when the compressed air supply is interrupted. It is formally defined in Table 94.
Table 94 – CompressedAirSupplyInterruptedAlarmType Definition
Attribute |
Value |
||||
BrowseName |
CompressedAirSupplyInterruptedAlarmType |
||||
IsAbstract |
False |
||||
References |
Node Class |
BrowseName |
DataType |
TypeDefinition |
Other |
Subtype of the OffNormalAlarmType defined in OPC 10000-9 |
|||||
Conformance Units |
|||||
|
The FilterAidDeviceStatusChangedConditionType is triggered when the FilterAidDeviceStatus of the FilterAidDeviceType changes. It is formally defined in Table 95.
Table 95 – FilterAidDeviceStatusChangedConditionType Definition
Attribute |
Value |
||||
BrowseName |
FilterAidDeviceStatusChangedConditionType |
||||
IsAbstract |
False |
||||
References |
Node Class |
BrowseName |
DataType |
TypeDefinition |
Other |
Subtype of the ConditionType defined in OPC 10000-9 |
|||||
0:HasProperty |
Variable |
Status |
FilterAidDeviceStatusEnum |
0:PropertyType |
M,R |
Conformance Units |
|||||
|
The property Status reflects the value of the FilterAidDeviceStatus property at the time the condition was triggered.
The CleaningUnitActiveConditionType is triggered when a cleaning cycle is started or stopped. It is formally defined in Table 96.
Table 96 – CleaningUnitActiveConditionType Definition
Attribute |
Value |
||||
BrowseName |
CleaningUnitActiveConditionType |
||||
IsAbstract |
False |
||||
References |
Node Class |
BrowseName |
DataType |
TypeDefinition |
Other |
Subtype of the ConditionType defined in OPC 10000-9 |
|||||
0:HasProperty |
Variable |
Active |
0:Boolean |
0:PropertyType |
M,R |
Conformance Units |
|||||
|
The property Active reflects the value of the CleaningActive property of the CleaningUnitType at the time the condition was triggered.
The CleaningRecommendedConditionType is triggered by the cleaning unit when cleaning of the separator is recommended. It is formally defined in Table 97.
Table 97 – CleaningRecommendedConditionType Definition
Attribute |
Value |
||||
BrowseName |
CleaningRecommendedConditionType |
||||
IsAbstract |
False |
||||
References |
Node Class |
BrowseName |
DataType |
TypeDefinition |
Other |
Subtype of the AcknowledgeableConditionType defined in OPC 10000-9 |
|||||
0:HasProperty |
Variable |
Recommended |
0:Boolean |
0:PropertyType |
M,R |
Conformance Units |
|||||
|
The Recommended property reflects the value of the property CleaningRecommended of the CleaningUnitType.
The AirConnectionStatusChangedConditionType is triggered when the ConnectionOpen variable of the AirConnectionType changes. It is formally defined in Table 98.
Table 98 – AirConnectionStatusChangedConditionType Definition
Attribute |
Value |
||||
BrowseName |
AirConnectionStatusChangedConditionType |
||||
IsAbstract |
False |
||||
References |
Node Class |
BrowseName |
DataType |
TypeDefinition |
Other |
Subtype of the ConditionType defined in OPC 10000-9 |
|||||
0:HasProperty |
Variable |
Status |
AirConnectionOpenEnum |
0:PropertyType |
M,R |
Conformance Units |
|||||
|
The Status property reflects the value of the ConnectionOpen property at the time the event is triggered.
The SafetySystemTriggeredAlarmType is sent when the safety system is triggered. It is formally defined in Table 99.
Table 99 – SafetySystemTriggeredAlarmType Definition
Attribute |
Value |
||||
BrowseName |
SafetySystemTriggeredAlarmType |
||||
IsAbstract |
False |
||||
References |
Node Class |
BrowseName |
DataType |
TypeDefinition |
Other |
Subtype of the OffNormalAlarmType defined in OPC 10000-9 |
|||||
Conformance Units |
|||||
|