The TemperatureRegulatorType represents a device for regulating the temperature of the process gas and is formally defined in Table 42.
Table 42 – TemperatureRegulatorType Definition
Attribute |
Value |
||||
BrowseName |
TemperatureRegulatorType |
||||
IsAbstract |
False |
||||
References |
Node Class |
BrowseName |
DataType |
TypeDefinition |
Other |
Subtype of the BaseObjectType defined in OPC 10000-5 |
|||||
0:HasAddIn |
Object |
2:Identification |
|
4:MachineryComponentIdentificationType |
O |
0:HasProperty |
Variable |
Malfunction |
0:Boolean |
0:PropertyType |
O,R |
0:HasAddIn |
Object |
4:MachineryItemState |
|
4:MachineryItemState_StateMachineType |
O |
0:HasComponent |
Object |
Temperature |
|
SensorSetpointWriteType |
O |
0:HasComponent |
Object |
PowerConsumption |
|
ConsumptionType |
O |
GeneratesEvent |
ObjectType |
MalfunctionAlarmType |
|
|
|
Conformance Units |
|||||
PAEFS TemperatureRegulatorType Basic |
|||||
PAEFS TemperatureRegulatorType Advanced |
|||||
PAEFS TemperatureRegulatorType Events |
|||||
PAEFS Additional Statemachines |
Table 43 – TemperatureRegulatorType Attribute values for child nodes
BrowsePath |
Description Attribute |
2:Identification |
Data for component identification (OPC 40001-1). |
Malfunction |
Indicates whether there is an error with the temperature regulator. True in case of error. |
4:MachineryItemState |
StateMachine representing the operating state of the temperature regulator (OPC 40001-1). |
Temperature |
Temperature of the process gas. |
PowerConsumption |
Contains information regarding the energy consumption of the temperature regulator. |
The server sends a MalfunctionAlarmType event when the Malfunction property changes.