The TotalizerVariableType provides means to summarize pulses. The TotalizerVariableType is a subtype of the AnalogSignalVariableType. It is formally defined in Table 184.
Table 184 – TotalizerVariableType definition
Attribute |
Value |
||||
BrowseName |
TotalizerVariableType |
||||
IsAbstract |
False |
||||
ValueRank |
−2 (−2 = ‘Any’) |
||||
DataType |
Number |
||||
References |
NodeClass |
BrowseName |
DataType |
TypeDefinition |
Other |
Subtype of AnalogSignalVariableType defined in 8.2, i.e. inheriting the InstanceDeclarations of that Node |
|||||
0:HasProperty |
Variable |
PulseValue |
0:Number |
0:PropertyType |
M |
0:HasProperty |
Variable |
PulseWidth |
0:Float |
0:PropertyType |
M |
Conformance Units |
|||||
PA-DIM TotalizerVariable |
This type defines a totalizer value.
For TotalizerVariableType there are two possible IRDIs as target of the HasDictionaryEntry reference, depending on the type of the totalized quantity. In case of mass totalization the IRDI 3:0112/2///61987#ABH327#001 shall be referenced, in case of actual volume totalization the IRDI 3:0112/2///61987#ABH328#001 shall be referenced. The related HasDictionaryEntry reference shall be defined after the concrete totalizer type is known.
PulseValue: ABA418#002 defines mass quantity assigned to one pulse. The default value is 1 pulse per 0.1 kg. The unit is fixed to kg.
PulseValue: ABE882#002 defines volume quantity assigned to one pulse. The default value is 1 pulse per 0.1 l. The unit is fixed to l.
PulseWidth: ABA635#003 defines setting of the pulse width. The unit is fixed to ms.
The components of TotalizerVariableType have additional references which are defined in Table 185.
Table 185 – TotalizerVariableType additional References
SourceBrowsePath |
Reference Type |
Is Forward |
TargetBrowsePath |
PulseWidth |
0:HasDictionaryEntry |
True |
For PulseValue there are two possible IRDIs as target of the HasDictionaryEntry reference, depending on the type of the totalized quantity. The dictionary entry for PulseValue shall be 3:0112/2///61987#ABA418#002 for mass flow and 3:0112/2///61987#ABE882#002 for volume flow.
The child Nodes of the TotalizerVariableType have additional Attribute values defined in Table 186.
Table 186 – TotalizerVariableType Attribute values for child Nodes
BrowsePath |
Value Attribute |
PulseWidth |
0.5 |