The FlameIonisationDetectorType is a subtype of the ProcessAnalyserType. It is formally defined in Table 83.
Table 83 – FlameIonisationDetectorType definition
Attribute |
Value |
||||
BrowseName |
FlameIonisationDetectorType |
||||
IsAbstract |
False |
||||
References |
NodeClass |
BrowseName |
DataType |
TypeDefinition |
Other |
Subtype of ProcessAnalyserType defined in 7.3, i.e. inheriting the InstanceDeclarations of that Node |
|||||
0:HasComponent |
Object |
DeviceConditionSet |
|
0:BaseObjectType |
O |
0:HasDictionaryEntry |
Object |
3:0112/2///61987#ABP410#001 |
|
0:IrdiDictionaryEntryType |
|
Conformance Units |
|||||
PA-DIM FlameIonisationDetectorType |
|||||
PA-DIM FlameIonisationDetectorType CatalystTemperature |
|||||
PA-DIM FlameIonisationDetectorType FuelGasPressure |
|||||
PA-DIM FlameIonisationDetectorType CombustionAirPressure |
|||||
PA-DIM FlameIonisationDetectorType BlockTemperature |
3:0112/2///61987#ABP410#001 is an FID device specific manifestation of the 3:<DictionaryEntryName> placeholder described in PADIMType.
FlameIonisationDetectorType is defined by IRDI as ABP410#001 which states “process analyser that uses flame ionisation to measure the concentration of one or more components in a gas phase”.
DeviceConditionSet is a container object for the condition parameters of the device. It is inherited from PADIMType and has an additional interface reference to IFlameIonisationDeviceConditionSetType to add FID device specific condition variables.
The components of FlameIonisationDetectorType have additional references which are defined in Table 84.
Table 84 – FlameIonisationDetectorType additional References
SourceBrowsePath |
Reference Type |
Is Forward |
TargetBrowsePath |
|||
DeviceConditionSet |
0:HasInterface |
True |
IFlameIonisationDeviceConditionSetType |
|||
|
0:HasDictionaryEntry |
True |
||||
|
0:HasDictionaryEntry |
True |
||||
|
0:HasDictionaryEntry |
True |
||||
|
0:HasDictionaryEntry |
True |
The components of FlameIonisationDetectorType have additional subcomponents which are defined in Table 85.
Table 85 – FlameIonisationDetectorType additional subcomponents
BrowsePath |
References |
NodeClass |
BrowseName |
DataType |
TypeDefinition |
Others |
DeviceConditionSet |
0:HasComponent |
Variable |
CatalystTemperature |
0:Float |
0:AnalogUnitType |
O |
DeviceConditionSet |
0:HasComponent |
Variable |
FuelGasPressure |
0:Float |
0:AnalogUnitType |
O |
DeviceConditionSet |
0:HasComponent |
Variable |
CombustionAirPressure |
0:Float |
0:AnalogUnitType |
O |
DeviceConditionSet |
0:HasComponent |
Variable |
BlockTemperature |
0:Float |
0:AnalogUnitType |
O |
The child Nodes of the FlameIonisationDetectorType have additional Attribute values defined in Table 86.
Table 86 – FlameIonisationDetectorType Attribute values for child Nodes
BrowsePath |
Value Attribute |
|||
|
0.0 |
|||
|
NamespaceUri: http://www.opcfoundation.org/UA/units/un/cefactUnitId: 4408652DisplayName: °CDescription: degree Celsius |
|||
|
0.0 |
|||
|
NamespaceUri: http://www.opcfoundation.org/UA/units/un/cefactUnitId: 5063250DisplayName: mbarDescription: millibar |
|||
|
0.0 |
|||
|
NamespaceUri: http://www.opcfoundation.org/UA/units/un/cefactUnitId: 5063250DisplayName: mbarDescription: millibar |
|||
|
0.0 |
|||
|
NamespaceUri: http://www.opcfoundation.org/UA/units/un/cefactUnitId: 4408652DisplayName: °CDescription: degree Celsius |