IO-Link uses in several places an octet to represent a duration in ms (e.g. MasterCycleTime and OffsetTime). As a time base and a multiplier is used, not all possible values are represented. The OPC UA DataType Duration uses a higher resolution.
If the client writes a value that cannot exactly be mapped, the server shall use the next possible lower value.
If the client tries to write a value outside the allowed range (either because of the larger size of the DataType or based on further limitations defined by the IO-Link Specification), the server shall return the error code “Bad_OutOfRange”.