The DeviceHealth Property defined in 4.5.4 provides a basic way to expose the health state of a device based on NAMUR NE 107.
This section defines AlarmTypes that can be used to indicate an abnormal device condition together with diagnostic information text as defined by NAMUR NE 107 as well as additional manufacturer specific information.
Figure 15 informally describes the AlarmTypes for DeviceHealth.
Figure 15 – Device Health Alarm type hierarchy
The DeviceHealthDiagnosticAlarmType is a specialization of the InstrumentDiagnosticAlarmType intended to represent abnormal device conditions as defined by NAMUR NE 107. This type can be used in filters for monitored items. Only subtypes of this type will be used in actual implementations. The Alarm becomes active when the device condition is abnormal. It is formally defined in Table 31.
Table 31 – DeviceHealthDiagnosticAlarmType definition
Attribute |
Value |
||||
BrowseName |
DeviceHealthDiagnosticAlarmType |
||||
IsAbstract |
True |
||||
References |
NodeClass |
BrowseName |
DataType |
TypeDefinition |
ModellingRule |
Subtype of the InstrumentDiagnosticAlarmType defined in OPC 10000-9. |
|||||
HasSubtype |
ObjectType |
FailureAlarmType |
Defined in clause 4.12.3 |
||
HasSubtype |
ObjectType |
CheckFunctionAlarmType |
Defined in clause 4.12.4 |
||
HasSubtype |
ObjectType |
OffSpecAlarmType |
Defined in clause 4.12.5 |
||
HasSubtype |
ObjectType |
MaintenanceRequiredAlarmType |
Defined in clause 4.12.6 |
||
Conformance Units |
|||||
DI HealthDiagnosticsAlarm |
Conditions of subtypes of DeviceHealthDiagnosticAlarmType become active when the device enters the corresponding abnormal state.
The Message field in the Event notification shall be used for additional information associated with the health status (e.g. the possible cause of the abnormal state and suggested actions to return to normal).
A Device may be in more than one abnormal state at a time in which case multiple Conditions will be active.
The FailureAlarmType is formally defined in Table 32. For description of the FAILURE state see Table 22.
Table 32 – FailureAlarmType definition
Attribute |
Value |
||||
BrowseName |
FailureAlarmType |
||||
IsAbstract |
False |
||||
References |
NodeClass |
BrowseName |
DataType |
TypeDefinition |
ModellingRule |
Subtype of the DeviceHealthDiagnosticAlarmType defined in 4.12.2. |
|||||
|
|
|
|
||
Conformance Units |
|||||
DI HealthDiagnosticsAlarm |
The CheckFunctionAlarmType is formally defined in Table 33. For description of the CHECK_FUNCTION state see Table 22.
Table 33 – CheckFunctionAlarmType definition
Attribute |
Value |
||||
BrowseName |
CheckFunctionAlarmType |
||||
IsAbstract |
False |
||||
References |
NodeClass |
BrowseName |
DataType |
TypeDefinition |
ModellingRule |
Subtype of the DeviceHealthDiagnosticAlarmType defined in 4.12.2. |
|||||
|
|
|
|
||
Conformance Units |
|||||
DI HealthDiagnosticsAlarm |
The OffSpecAlarmType is formally defined in Table 34. For description of the OFF_SPEC state see Table 22.
Table 34 – OffSpecAlarmType definition
Attribute |
Value |
||||
BrowseName |
OffSpecAlarmType |
||||
IsAbstract |
False |
||||
References |
NodeClass |
BrowseName |
DataType |
TypeDefinition |
ModellingRule |
Subtype of the DeviceHealthDiagnosticAlarmType defined in 4.12.2. |
|||||
|
|
|
|
||
Conformance Units |
|||||
DI HealthDiagnosticsAlarm |
The MaintenanceRequiredAlarmType is formally defined in Table 35. For description of the MAINTENANCE_REQUIRED state see Table 22.
Table 35 – MaintenanceRequiredAlarmType definition
Attribute |
Value |
||||
BrowseName |
MaintenanceRequiredAlarmType |
||||
IsAbstract |
False |
||||
References |
NodeClass |
BrowseName |
DataType |
TypeDefinition |
ModellingRule |
Subtype of the DeviceHealthDiagnosticAlarmType defined in 4.12.2. |
|||||
|
|
|
|
||
Conformance Units |
|||||
DI HealthDiagnosticsAlarm |