The Reset2 Method extends the Reset Method, by adding an optional Comment. For other functionality see the Reset Method definition.

Signature

Reset2(

[in] LocalizedTextComment

);

The parameters are defined in Table 4646.

Table 4646 – Reset2 Method parameters

Argument

Description

Comment

A localized text that shall be applied to the Condition.

If the Comment argument is NULL (both locale and text are empty) it shall be ignored and any existing comments will remain unchanged. To reset the comment, an empty text with a locale shall be provided.

Method result codes in Table 4747 (defined in Call service)

Table 4747 – Reset2 result codes

Result Code

Description

Bad_MethodInvalid

The MethodId provided does not correspond to the ObjectId provided. See 10000-4 for the general description of this result code.

Bad_NodeIdInvalid

Used to indicate that the specified ObjectId is not valid or that the Method was called on the AlarmConditionType Node.

See 10000-4 for the general description of this result code.

Bad_InvalidState

The Alarm instance was not latched or is still active or still requires acknowledgement / confirmation. To reset an Alarm Instance it shall have been in Alarm, and returned to normal and have been acknowledged/confirmed prior to being reset.

Bad_InvalidArgument

The Comment string provided exceeds the allowed length for the comment or is invalid in some other manner.

Table 4848 specifies the AddressSpace representation for the Reset2 Method.

Table 4848 – Reset2 Method AddressSpace definition

Attribute

Value

BrowseName

Reset2

References

NodeClass

BrowseName

DataType

TypeDefinition

ModellingRule

HasProperty

Variable

InputArguments

Argument[]

PropertyType

Mandatory

AlwaysGeneratesEvent

ObjectType

AuditConditionResetEventType

Defined in 5.10.11

ConformanceUnits

A & C Latched State

If Auditing is supported, this Method shall generate an Event of AuditConditionResetEventType for all invocations of the Method.