The Reset2 Method extends the Reset Method, by adding an optional Comment. For other functionality see the Reset Method definition.

Signature

Reset2(

[in] LocalizedTextComment

);

The parameters are defined in Table 48.

Table 48 – Reset2 Method parameters

Argument

Description

Comment

A localized text to be applied to the Condition.

If the Comment argument is NULL (both locale and text are empty) it will be ignored and any existing comments will remain unchanged. If the comment is to be reset, an empty text with a locale shall be provided.

Method result codes in Table 49 (defined in Call service)

Table 49 – Reset2 result codes

Result Code

Description

Bad_MethodInvalid

The MethodId provided does not correspond to the ObjectId provided. See 10000-4 for the general description of this result code.

Bad_NodeIdInvalid

Used to indicate that the specified ObjectId is not valid or that the Method was called on the AlarmConditionType Node.

See 10000-4 for the general description of this result code.

Bad_InvalidState

The Alarm instance was not latched or is still active or still requires acknowledgement / confirmation. For an Alarm Instance to be reset it must have been in Alarm, and returned to normal and have been acknowledged/confirmed prior to being reset.

Table 50 specifies the AddressSpace representation for the Reset2 Method.

Table 50 – Reset2 Method AddressSpace definition

Attribute

Value

BrowseName

Reset2

References

NodeClass

BrowseName

DataType

TypeDefinition

ModellingRule

HasProperty

Variable

InputArguments

Argument[]

PropertyType

Mandatory

AlwaysGeneratesEvent

ObjectType

AuditConditionResetEventType

Defined in 5.10.11

ConformanceUnits

A & C Latched State

If Auditing is supported, this Method shall generate an Event of AuditConditionResetEventType for all invocations of the Method.