The Reset Method is used reset all of the counters, rates and time in the Object
Signature
Reset();
Method Result Codes in Table 5151 (defined in Call Service)
Table 147147 – Suppress result codes
|
Result Code |
Description |
|
Bad_MethodInvalid |
The MethodId provided does not correspond to the ObjectId provided. See 10000-4 for the general description of this result code. |
|
Bad_NodeIdInvalid |
Used to indicate that the specified ObjectId is not valid. See 10000-4 for the general description of this result code. |
Comments
The Reset Method will clear all setting in the diagnostic object and initialize them to zero.
Table 148148 specifies the AddressSpace representation for the Reset Method.
Table 148148 – Reset Method AddressSpace Definition
|
Attribute |
Value |
||||
|
BrowseName |
Reset |
||||
|
References |
NodeClass |
BrowseName |
DataType |
TypeDefinition |
ModellingRule |
|
|
|
|
|
|
|
|
AlwaysGeneratesEvent |
ObjectType |
AuditUpdateMethodEventType |
Defined in 10000-5 |
||
|
ConformanceUnits |
|||||
|
A & C Alarm Metrics |
|||||
If Auditing is supported, this Method shall generate an Event of AuditConditionMethodEventType for all invocations of the Method.