5.8.23.3 ExclusiveRateOfChangeAlarmType

ExclusiveRateOfChangeAlarmType is utilized with multiple mutually exclusive limits. It is formally defined in Table 104.

Table 104 – ExclusiveRateOfChangeAlarmType definition

Attribute

Value

BrowseName

ExclusiveRateOfChangeAlarmType

IsAbstract

False

References

NodeClass

BrowseName

DataType

TypeDefinition

ModellingRule

Inherits the Properties of the ExclusiveLimitAlarmType defined in clause 5.8.19.3.

HasProperty

Variable

EngineeringUnits

EUInformation

PropertyType

Optional

ConformanceUnits

A & C Exclusive RateOfChange

EngineeringUnits provides the engineering units associated with the limits values. If this is not provided the assumed Engineering Unit is the same as the EU associated with the parent variable per second e.g. if parent is meters, this unit is meters/second.