5.8.23.2 NonExclusiveRateOfChangeAlarmType

The NonExclusiveRateOfChangeAlarmType is a special level Alarm utilized with one or more non-exclusive states. If for example both the High and HighHigh states need to be maintained as active at the same time this AlarmConditionType should be used

The NonExclusiveRateOfChangeAlarmType is based on the NonExclusiveLimitAlarmType. It is formally defined in Table 103.

Table 103 – NonExclusiveRateOfChangeAlarmType definition

Attribute

Value

BrowseName

NonExclusiveRateOfChangeAlarmType

IsAbstract

False

References

NodeClass

BrowseName

DataType

TypeDefinition

ModellingRule

Subtype of the NonExclusiveLimitAlarmType defined in clause 5.8.20.

HasProperty

Variable

EngineeringUnits

EUInformation

PropertyType

Optional

ConformanceUnits

A & C Non-Exclusive RateOfChange

EngineeringUnits provides the engineering units associated with the limits values. If this is not provided the assumed Engineering Unit is the same as the EU associated with the parent variable per second e.g. if parent is meters, this unit is meters/second.