5.4.3.23 DurationInStateNonZero

The DurationInStateNonZero Aggregate defined in Table 34 returns the time Duration during the interval that the Variable was in the one state. The Simple Bounding Values for the interval are used to determine initial value (start time < end time) or ending value (if start time > end time). If one or more raw values are non-Good, they are not included in the Duration, and the Aggregate StatusCode is determined using the StatusCode Calculation (see 5.3) for time based Aggregates.

Duration is in milliseconds. Unless otherwise indicated, StatusCodes are Good, Calculated.

Table 34 – DurationInStateNonZero Aggregate summary

DurationInStateNonZero Aggregate Characteristics

Type

Calculated

Data Type

Duration

Use Bounds

Simple

Timestamp

StartTime

StatusCode Calculations

Calculation Method

PercentTime

Partial

Set Sometimes

If an interval is not a complete interval

Calculated

Set Always

Interpolated

Not Set

Raw

Not Set

Multi Value

Not Set

StatusCode Common Special Cases

Before Start of Data

Bad_NoData

After End of Data

Bad_NoData

No Start Bound

Treat the beginning value as Bad_NoData and compute the Aggregate

No End Bound

Treat the ending value as Bad_NoData and compute the Aggregate

Bound Bad

Use as value and compute the Aggregate as defined

Bound Uncertain

Use as value and compute the Aggregate as defined