The Compressed Air System and Airnets are identified by an Identification Object of the CASIdentificationType which uses the Interface ITagNameplateType and its Properties.

The Main Control System is identified by an Identification Object of the MachineryComponentIdentificationType.

Components are identified by an Identification Object of a subtype of the abstract MachineryItemIdentificationType defined by OPC UA for Machinery (OPC 40001-1). The MachineryItemIdentificationType and its subtypes provide the capabilities to globally uniquely identify the Component and have access to vendor defined information about the Component and manage user-specific information for the identification of the Component. When instantiating a Component, the Identification Object must use an appropriate subtype of the MachineryItemIdentificationType.

For all Components and the Main Control System the DeviceClass Property has its Value Attribute set to a mandatory specific value and its ModellingRule changed to mandatory.

Table 9 shows for each CASPart what value shall be set for different applications like the DeviceClass, BrowseName and GroupName.

Table 9 – DeviceClass, BrowseName and GroupName for CASParts

CASPart Name

DeviceClass

BrowseName

GroupName

Airnet

-

Airnet

Airnets

Charging System

Charging system

ChargingSystem

ChargingSystems

Compressor

Compressor

Compressor

Compressors

Condensate Drain

Condensate drain

CondensateDrain

CondensateDrains

Condensate Separator

Condensate separator

CondensateSeparator

CondensateSeparators

Converter

Converter

Converter

Converters

Cooling System

Cooling system

CoolingSystem

CoolingSystems

Dryer

Dryer

Dryer

Dryers

Filter

Filter

Filter

Filters

Heat Recovery System

Heat recovery system

HeatRecoverySystem

HeatRecoverySystems

Main Control System

MCS

MCS

-

Receiver

Receiver

Receiver

Receivers

Sensor

Sensor

Sensor

Sensors

Valve

Valve

Valve

Valves

For Components that are not defined by this specification, the DeviceClass Property shall be mandatory as well. The value shall match the name of the new Component.

All properties of the MachineryItemIdentificationType and its subtypes shall be used as intended by the OPC UA for Machinery (OPC 40001-1) specification.

To comply with the Finding all Machines in a Server use case of the OPC UA for Machinery (OPC 40001-1) specification, all Components that are considered as machines by their manufacturer or the customer shall be added to the Machines Object defined in OPC 40001-1 and use the MachineIdentificationType as TypeDefinition for their Identification Object. The Compressed Air System, the Main Control System, and Airnets are not considered as machine in the sense of OPC 40001-1, whereas the following Components may be considered as machines in this context (this list is not exhaustive):