The CompressorOperationalType extends its supertype by compressor specific Variables and is formally defined in Table 99.
Table 99 – CompressorOperationalType Definition
Attribute |
Value |
||||
BrowseName |
CompressorOperationalType |
||||
IsAbstract |
False |
||||
References |
Node Class |
BrowseName |
DataType |
TypeDefinition |
Other |
Subtype of the OperationalType defined in 7.45, i.e. inheriting the InstanceDeclarations of that Node. |
|||||
0:HasComponent |
Variable |
ActivePressureBand |
0:UInt16 |
0:DataItemType |
O, RO |
0:HasComponent |
Variable |
FlowRateRatio |
0:Double |
0:BaseAnalogType |
O, RO |
0:HasComponent |
Variable |
IsentropicEfficiency |
0:Double |
0:BaseAnalogType |
O, RO |
0:HasComponent |
Variable |
SpecificEnergyRequirement |
0:Double |
0:BaseAnalogType |
O, RO |
|
|
|
|
|
|
The following nodes override nodes added by the OperationalType |
|||||
0:HasComponent |
Variable |
OperatingState |
CompressorOperatingStateEnum |
0:DataItemType |
O, RO |
The following illustration of a state machine does not imply the actual function or state machine for a compressor. It serves as an example of how the actual state machines may function.
Figure 32 – CompressorOperationalType State Machine Illustration
The InstanceDeclarations of the CompressorOperationalType have additional Attributes defined in Table 100.
Table 100 – CompressorOperationalType Attribute values for child Nodes
Source Path |
Value Attribute |
Description |
ActivePressureBand |
|
Indicates the actual active pressure band. |
FlowRateRatio |
|
Calculated ratio of actual and maximum possible flow rate of a compressor. |
IsentropicEfficiency |
|
Calculated isentropic efficiency. |
OperatingState |
|
Actual operating state of the compressor. |
SpecificEnergyRequirement |
|
Calculated shaft input energy per unit of compressor actual rate of flow. |