The instance declaration Object EventReporting overrides definitions of the BACnetEventReportingType.
The EventAlgorithm component is changed to TypeDefinition BACnetCommandFailureAlgorithmType and ModellingRule Mandatory if used in the BACnetMultiStateOutputType. The BACnetCommandFailureAlgorithmType is defined in 8.10.
This OPC UA Property, of DataType String, represents the BACnet property Device_Type.
It is a text description of the physical device connected to the multi-state output.
This OPC UA Property, of DataType BACnetPriorityValue [16], represents the BACnet property Priority_Array. The BACnetPriorityValue DataType is defined in 10.6.4.
It is an array that contains prioritized commands that are in effect for this object. See 3.2.1 for details on command prioritization.
This OPC UA Property, of DataType 0:UInteger, represents the BACnet property Relinquish_Default.
It is the default value to be used for the Present_Value when all command priority values in the Priority_Array have a NULL value. See 3.2.1 for details on command prioritization.
This OPC UA Property, of type 0:UInteger, is an indication of the actual value of the entity controlled by Present_Value.