This is a subtype of AlarmGroupType that can be used to suppress other alarms. This subtype of AlarmGroup extends the AlarmGroupType to allow the addition of Variables that have a Boolean DataType. The Variable can be thought of as representing the Id of the ActiveState of an Alarm, i.e. when any of the included Variables have a value of true the AlarmSuppressionGroup is active.
Table 45 – AlarmSuppressionGroupType definition
Attribute |
Value |
||||
BrowseName |
AlarmSuppressionGroupType |
||||
IsAbstract |
False |
||||
References |
NodeClass |
BrowseName |
DataType |
TypeDefinition |
ModellingRule |
Subtype of the AlarmGroupType |
|||||
AlarmSuppressionGroupMember |
Variable |
<DigitalVariable> |
Boolean |
BaseDataVariableType |
OptionalPlaceholder |
ConformanceUnits |
|||||
A & C Suppression Group |
The instance of an AlarmSuppressionGroupType should be given a name and description that describes the purpose of the Alarm group.
The AlarmSuppressionGroupType instance will contain a list of instances of AlarmConditionType or sub type of AlarmConditionType or BaseDataVaribleType with a DataType of Boolean referenced by AlarmSuppressionGroupMember references. At least one Node must be present in an instance of an AlarmGroupType.