6 Profiles ToC Previous

6.6 Profile tables ToC Previous

6.6.31 A & C Alarm Server Facet ToC Previous Next

Table 53 describes the details of the A & C Alarm Server Facet. This Facet requires support for Alarms. Alarms extend the ConditionType by adding an Active state which indicates when something in the system requires attention by an Operator. This Facet builds upon the A&C Base Condition Server Facet. This facet requires that discrete AlarmTypes be supported, it also allows for optional support of shelving, alarm comments and other discrete AlarmTypes such as Trip or Off-Normal.

Table 53 – A & C Alarm Server Facet

Group Conformance Unit / Profile Title Optional
Profile A & C Base Condition Server Facet False
Alarms   and Conditions A & C Alarm False
Alarms   and Conditions A & C Audible Sound True
Alarms   and Conditions A & C Comment True
Alarms   and Conditions A & C Discrepancy True
Alarms   and Conditions A & C Discrete False
Alarms   and Conditions A & C First in Group Alarm True
Alarms   and Conditions A & C OffNormal True
Alarms   and Conditions A & C On-Off Delay True
Alarms   and Conditions A & C Out Of Service True
Alarms   and Conditions A & C Re-Alarming True
Alarms   and Conditions A & C Shelving True
Alarms   and Conditions A & C Silencing True
Alarms   and Conditions A & C Suppression True
Alarms   and Conditions A & C Suppression by Operator True
Alarms   and Conditions A & C SystemOffNormal True
Alarms   and Conditions A & C Trip True

Previous Next