Search
3 result(s) for SetStoredVariables
-
OPC-10000-81 – OPC Unified Architecture - Part 81: UAFX Connecting Devices and Information Model6.2.4.3.7 Command SetConfigurationDataCmdeach element in ConfigurationData . If the ConnectionEndpoint related to ConfigurationData has IsPersistent set, SetStoredVariables (see 6.4.6.3 ) shall be called for all Variables indicated by Key having the NonVolatile
-
OPC-10000-81 – OPC Unified Architecture - Part 81: UAFX Connecting Devices and Information ModelVariable 3:<ConfigurationVariable1> 0:BaseDataType 0:BaseDataVariableType OP 0:HasComponent Method 3:SetStoredVariables Defined in 6.4.6.3 O 0:HasComponent Method 3:ClearStoredVariables Defined in 6.4.6.4 O 0:HasComponent ... FunctionalGroups . This will also assist with the uniqueness requirement for BrowseNames . The optional Methods SetStoredVariables , ClearStoredVariables , and ListStoredVariables allow for the maintenance of storage for configuration Variables . If storage
-
OPC-10000-81 – OPC Unified Architecture - Part 81: UAFX Connecting Devices and Information Model6.4.6.3 SetStoredVariables methodSetStoredVariables method The optional SetStoredVariables Method allows a Client to store current values of configuration Variables for the FunctionalEntity and its SubFunctionalEntities . The FunctionalEntity shall apply the stored values ... this Method is specified below; the arguments are defined in Table 50 . Signature SetStoredVariables ( [in] 0:NodeId[] VariablesToStore, [out] 0:StatusCode[] Results ); Table 50 - SetStoredVariables Method arguments Argument Description VariablesToStore