BACnetReliability

http://opcfoundation.org/UA/BACnet_V2/

2.0.0

2022-10-18


NodeId ns=1;i=3001
NodeClass DataType
BrowseName 1:BACnetReliability
DisplayName BACnetReliability
BaseType 0:Enumeration
IsAbstract False
Name Value Description
NoFaultDetected 0 The present value is reliable; that is, no other fault has been detected.
NoSensor 1 No sensor is connected to the Input object.
OverRange 2 The sensor connected to the Input is reading a value higher than the normal operating range. If the object is a Binary Input, this is possible when the Binary state is derived from an analog sensor or a binary input equipped with electrical loop supervision circuits.
UnderRange 3 The sensor connected to the Input is reading a value lower than the normal operating range. If the object is a Binary Input, this is possible when the Binary Input is actually a binary state calculated from an analog sensor.
OpenLoop 4 The connection between the defined object and the physical device is providing a value indicating an open circuit condition.
ShortedLoop 5 The connection between the defined object and the physical device is providing a value indicating a short circuit condition.
NoOutput 6 No physical device is connected to the Output object.
UnreliableOther 7 The controller has detected that the present value is unreliable, but none of the other conditions describe the nature of the problem. A generic fault other than those listed above has been detected, e.g., a Binary Input is not cycling as expected.
ProcessError 8 A processing error was encountered.
MultiStateFault 9 The FAULT_STATE, FAULT_LIFE_SAFETY or FAULT_CHARACTERSTRING fault algorithm has evaluated a fault condition.
ConfigurationError 10 The object's properties are not in a consistent state.
CommunicationFailure 12 Proper operation of the object is dependent on communication with a remote sensor or device and communication with the remote sensor or device has been lost.
MemberFault 13 Indicates that the set of referenced member objects includes one or more Status_Flags properties whose FAULT flag value is equal to TRUE.
MONITORED_OBJECT_FAULT 14 Indicates that the monitored object is in fault.
TRIPPED 15 The end device, such as an actuator, is not responding to commands, prevented by a tripped condition or by being mechanically held open.
Reference NodeClass BrowseName TypeDefinition DataType Other
0:HasProperty Variable 0:EnumValues 0:PropertyType 0:EnumValueType[15]