7 OPC UA ObjectTypes ToC Previous Next

7.3 WSAlarmType ObjectType Definition ToC Previous Next

The WSAlarmType provides two variables to inform about the current alarm and is formally defined in Table 17.

The WSAlarmCode can be used to pass an integer to the client and map it to a language-specific message. WSAlarmMessage contains the message as localizedText.

For the future it is planned to use OPC UA functionalities like Alarms and Conditions for this data point. As soon as this is available in the Weihenstephan Standards, this object definition will be obsolete.

Table 17 – WSAlarmType Definiton

Attribute Value        
BrowseName WSAlarmType        
IsAbstract False        
References Node Class BrowseName DataType TypeDefinition Other
Subtype of the WSBaseObjectType          
0:HasComponent Variable WSAlarmCode UInt32 BaseDataVariableType M
0:HasComponent Variable WSAlarmMessage LocalizedText BaseDataVariableType O

WSAlarmCode shall be used to pass an integer to the client and map it to a language-specific message. If there ist no alarm, the value of the WSAlarmCode variable is set to 0.

WSAlarmMessage contains the message as localizedText. If there is no alarm, the value of the WSAlarmMessage variable is empty (empty string).

readme_files/image019.png Figure 13 – WSAlarmType