6 Information Models ToC Previous Next

6.2 Datatype Definition ToC Previous Next

6.2.1 InFlagsType ToC Previous Next

This is a subtype of the Byte DataType with the OptionSetValues Property defined. The InFlagsType is formally defined in Table 15.

Table 15 – InFlagsType Values

Value Bit No. Description
CommunicationError 0    0: No error1: An error was detected in the previous ResponseSPDU.
OperatorAckRequested 1 Used to inform the SafetyProvider that operator acknowledgment is requested.
FSV_Activated 2 Is used for conformance test of SafetyConsumer.SAPI.FSV_Activated

Bits 3..7 are reserved for future use shall be set to zero by the SafetyConsumer and shall not be evaluated by the SafetyProvider.

The InFlagsType representation in the AddressSpace is defined in Table 16.

Table 16 – InFlagsType Definition

Attribute Value
BrowseName InFlagsType
IsAbstract False

Subtype of the Byte DataType defined in OPC 10000-5

References NodeClass BrowseName DataType TypeDefinition Other
0:HasProperty Variable 0:OptionSetValues 0:LocalizedText [] 0:PropertyType  
Conformance Units          
SafetySupport          

NOTE: CommunicationError can be used as a trigger, e.g., for a communication analysis tool. It is not forwarded to the safety application by the SafetyProvider. If CommunicationError is needed in the safety application, bidirectional communication can be implemented and the value of CommunicationError can be put into the user data.