The SupervisionElectronicsType provides Variables used for monitoring the Pump electronics. It is formally defined in Table 43. For the generation of events, the SupervisionElectronicsType has references to the four Namur NE 107 statuses defined in OPC 10000-100. The InputNode Property of the Alarm shall contain the NodeId of the Component.
Table 43 – SupervisionElectronicsType Definition
Attribute |
Value |
||||
BrowseName |
SupervisionElectronicsType |
||||
IsAbstract |
false |
||||
References |
Node Class |
BrowseName |
DataType |
TypeDefinition |
Other |
Subtype of the 2:FunctionalGroupType defined in OPC 10000-100, i.e. inheriting the InstanceDeclarations of that Node. |
|||||
0:HasComponent |
Variable |
ArmatureCircuit |
0:Boolean |
0:TwoStateDiscreteType |
O, RO |
0:HasComponent |
Variable |
CurrentInsideDevice |
0:Boolean |
0:TwoStateDiscreteType |
O, RO |
0:HasComponent |
Variable |
ElectricalFault |
0:Boolean |
0:TwoStateDiscreteType |
O, RO |
0:HasComponent |
Variable |
FieldCircuit |
0:Boolean |
0:TwoStateDiscreteType |
O, RO |
0:HasComponent |
Variable |
InstallationFault |
0:Boolean |
0:TwoStateDiscreteType |
O, RO |
0:HasComponent |
Variable |
InsulationResistance |
0:Boolean |
0:TwoStateDiscreteType |
O, RO |
0:HasComponent |
Variable |
PhaseFailure |
0:Boolean |
0:TwoStateDiscreteType |
O, RO |
0:HasComponent |
Variable |
ShortCircuit |
0:Boolean |
0:TwoStateDiscreteType |
O, RO |
0:HasComponent |
Variable |
ShortToEarth |
0:Boolean |
0:TwoStateDiscreteType |
O, RO |
0:HasComponent |
Variable |
SupplyCurrent |
0:Boolean |
0:TwoStateDiscreteType |
O, RO |
0:HasComponent |
Variable |
SupplyCurrentHigh |
0:Boolean |
0:TwoStateDiscreteType |
O, RO |
0:HasComponent |
Variable |
SupplyCurrentLow |
0:Boolean |
0:TwoStateDiscreteType |
O, RO |
0:HasComponent |
Variable |
SupplyFrequency |
0:Boolean |
0:TwoStateDiscreteType |
O, RO |
0:HasComponent |
Variable |
SupplyFrequencyHigh |
0:Boolean |
0:TwoStateDiscreteType |
O, RO |
0:HasComponent |
Variable |
SupplyFrequencyLow |
0:Boolean |
0:TwoStateDiscreteType |
O, RO |
0:HasComponent |
Variable |
SupplyVoltage |
0:Boolean |
0:TwoStateDiscreteType |
O, RO |
0:HasComponent |
Variable |
SupplyVoltageHigh |
0:Boolean |
0:TwoStateDiscreteType |
O, RO |
0:HasComponent |
Variable |
SupplyVoltageLow |
0:Boolean |
0:TwoStateDiscreteType |
O, RO |
0:HasComponent |
Variable |
VoltageInsideDevice |
0:Boolean |
0:TwoStateDiscreteType |
O, RO |
0:HasComponent |
Variable |
WindingTemperature |
0:Boolean |
0:TwoStateDiscreteType |
O, RO |
0:GeneratesEvent |
ObjectType |
2:CheckFunctionAlarmType |
Defined in OPC 10000-100 |
||
0:GeneratesEvent |
ObjectType |
2:FailureAlarmType |
Defined in OPC 10000-100 |
||
0:GeneratesEvent |
ObjectType |
2:MaintenanceRequiredAlarmType |
Defined in OPC 10000-100 |
||
0:GeneratesEvent |
ObjectType |
2:OffSpecAlarmType |
Defined in OPC 10000-100 |
The InstanceDeclarations of the SupervisionElectronicsType have additional Attributes defined in Table 44. The Variables and the associated Descriptions are based on the standard VDMA 24223-1.
Table 44 – SupervisionElectronicsType Attribute values for child Nodes
BrowsePath |
Description Attribute |
ArmatureCircuit |
This property indicates a failure in armature circuit. |
CurrentInsideDevice |
This property indicates unacceptable current inside the device. |
ElectricalFault |
This property indicates a generic electrical fault. |
FieldCircuit |
This property indicates a failure in field circuit. |
InstallationFault |
This property indicates an unacceptable electrical installation, e.g. mixed up phases. |
InsulationResistance |
This property indicates an unacceptable low winding resistance. |
PhaseFailure |
This property indicates a phase failure. |
ShortCircuit |
This property indicates a short circuit. |
ShortToEarth |
This property indicates a short to earth. |
SupplyCurrent |
This property indicates a failure of supply current. |
SupplyCurrentHigh |
This property indicates too high supply current. |
SupplyCurrentLow |
This property indicates too low supply current. |
SupplyFrequency |
This property indicates unacceptable supply frequency. |
SupplyFrequencyHigh |
This property indicates too high supply frequency. |
SupplyFrequencyLow |
This property indicates too low supply frequency. |
SupplyVoltage |
This property indicates a failure of supply voltage. |
SupplyVoltageHigh |
This property indicates too high supply voltage. |
SupplyVoltageLow |
This property indicates too low supply voltage. |
VoltageInsideDevice |
This property indicates unacceptable voltage inside the device. |
WindingTemperature |
This property indicates an unacceptable winding temperature. |