8.15 OperationModeEnum

The enumeration OperationModeEnum defines possible Pump operation modes in Table 142. The Values and the associated Descriptions are based on the standard VDMA 24223.

Table 142 – OperationModeEnum Items

Name

Value

Description

AutoControl

0

standard control algorithm, not configurable

ClosedLoopStandardPID

1

pid algorithm, control parameters configurable in functional element ControlPID

Advanced

2

manufacturer specific control algorithm, control parameters configurable

StandBy

3

ready for operation

OpenLoopMin

4

open loop operation at minimum characteristic

OpenLoopValue

5

open loop operation at set point value

OpenLoopMax

6

open loop operation at maximum characteristic

ClosedLoopMin

7

closed loop operation at minimum characteristic

ClosedLoopMax

8

closed loop operation at maximum characteristic

Test

9

Test operation

Calibration

10

Calibration mode

The OperationModeEnum representation in the AddressSpace is formally defined in Table 143.

Table 143 – OperationModeEnum Definition

Attribute

Value

BrowseName

OperationModeEnum

IsAbstract

False

References

Node Class

BrowseName

DataType

TypeDefinition

Other

Subtype of 0:Enumeration defined in OPC 10000-5.

0:HasProperty

Variable

0:EnumValues

0:EnumValueType[]

0:PropertyType