The OutletConnectionMeasurementsType provides Variables used for measurements performed at a Pump outlet connection and is formally defined in Table 112. For the generation of events, the OutletConnectionMeasurementsType has a reference to the 0:LimitAlarmType. The InputNode Property of the Alarm shall contain the NodeId of the Component. Measurements defined in this ObjectType have an additional Subcomponent with the TypeDefinition 0:PropertyType and the BrowseName KindOfQuantity defined in Table 113. In this Variables the measurements can be matched to a physical quantity. To comply with this Companion Specification, the default values for the Property 0:EngineeringUnits and the Property KindOfQuantity provided in Table 114 should be used. The values should be sensible to the use of the application.
Table 112 – OutletConnectionMeasurementsType Definition
| Attribute | Value | ||||
| BrowseName | OutletConnectionMeasurementsType | ||||
| IsAbstract | False | ||||
| References | Node Class | BrowseName | DataType | TypeDefinition | Other | 
| Subtype of the 2:FunctionalGroupType defined in OPC 10000-100, i.e. inheriting the InstanceDeclarations of that Node. | |||||
| 0: HasComponent | Variable | MeanVelocityAtOutlet | 0:Double | 0:BaseAnalogType | O, RO | 
| 0:HasComponent | Variable | OutletTemperatureOfThePump | 0:Double | 0:BaseAnalogType | O, RO | 
| 0:GeneratesEvent | ObjectType | 0:LimitAlarmType | Defined in OPC 10000-9 | ||
Table 113 – OutletConnectionMeasurementsType Additional Subcomponents
| Source Path | References | NodeClass | BrowseName | DataType | TypeDefinition | Other | 
| MeanVelocityAtOutlet | 0:HasProperty | Variable | KindOfQuantity | 0:String | 0:PropertyType | O, RO | 
| OutletTemperatureOfThePump | 0:HasProperty | Variable | KindOfQuantity | 0:String | 0:PropertyType | O, RO | 
The InstanceDeclarations of the OutletConnectionMeasurementsType have additional Attributes defined in Table 114. The Variables and the associated Descriptions are based on the standard DIN EN ISO 17769-1.
Table 114 – OutletConnectionMeasurementsType Attribute values for child Nodes
| BrowsePath | Value Attribute | Description Attribute | ||
| MeanVelocityAtOutlet | 
 | Measured rate of flow at pump outlet connection divided by the outlet area of the pump. | ||
| 
 
 | NamespaceUri: http://www.opcfoundation.org/UA/units/un/cefact UnitId: 5067859 DisplayName: m/s Description: metre per second | 
 | ||
| 
 
 | “velocity” | Vector quantity giving the rate of change of a position vector | ||
| OutletTemperatureOfThePump | 
 | Measured temperature acting at the outlet area of the pump. | ||
| 
 
 | NamespaceUri: http://www.opcfoundation.org/UA/units/un/cefact UnitId: 4932940 DisplayName: K Description: kelvin | 
 | ||
| 
 
 | “temperature” | Quantity representing a temperature value |