The RioFaDigitalOutputChannelType provides access to the data of a discrete RIO Output Channel according to RIOforFA.

Table 55 – RioFaDigitalOutputChannelType

Attribute

Value

BrowseName

RioFaDigitalOutputChannelType

IsAbstract

False

References

Node Class

BrowseName

DataType

TypeDefinition

Other

Subtype of the RioChannelType.

0:HasComponent

Variable

ProcessValue

RioFaDigitalProcessValueDataType

RioFaDigitalProcessValueVariableType

M, RO

0:HasComponent

Variable

ProcessValueReadback

RioFaDigitalProcessValueDataType

RioFaDigitalProcessValueVariableType

O, RO

0:HasComponent

Variable

SignalValue

0:Double

0:BaseAnalogType

O, RO

0:HasComponent

Variable

SignalValueReadback

0:Double

0:BaseAnalogType

O, RO

0:HasComponent

Variable

Config

RioFaDigitalOutputConfigDataType

RioFaDigitalOutputConfigVariableType

M, RO

Conformance Units

PNRIO Channel Objects

The ProcessValue Variable contains a Controller’s output data to an automated process.

The ProcessValueReadback Variable contains the readback value obtained by reading the output signal back through the Transducer and the Function Block.

The SignalValue Variable contains the output signal value fed to the signal coupling in the Transducer.

The SignalValueReadback Variable contains the output signal read back through the signal coupling in the Transducer.

The Config Variable contains the configuration properties available for the RIO Channel. See the definition of the RioFaDigitalOutputConfigVariableType (see chapter 9.4.4)