9.1 FactoryReset

FactoryReset is a method used to reset all or a predefined group of the device parameters to their factory settings. The desired reset mode is selected by the enumeration value of the input argument. Access to this method shall be restricted to authorized users.

The signature of this Method is specified below. Table 273 and Table 275 specify the Arguments and AddressSpace representation, respectively.

Signature

FactoryReset (

[in] ResetModeEnum ResetMode

);

Table 273 – FactoryReset Method Arguments

Argument

Description

ResetMode

The desired reset mode, see 10.1 for a definition of all available values.

Method Result Codes are defined in Table 274.

Table 274 – FactoryReset Method Result Codes (defined in Call Service)

Result Code

Description

Bad_InvalidArgument

The input is not a valid reset code.

Bad_UserAccessDenied

The current user does not have the rights required.

Table 275 – FactoryReset Method AddressSpace definition

Attribute

Value

BrowseName

FactoryReset

References

NodeClass

BrowseName

DataType

TypeDefinition

ModellingRule

0:HasProperty

Variable

0:InputArguments

0:Argument[]

0:PropertyType

0:Mandatory