The TocAnalyserType is a subtype of the ProcessAnalyserType. It is formally defined in Table 115.
Table 115 – TocAnalyserType definition
|
Attribute |
Value |
||||
|
BrowseName |
TocAnalyserType |
||||
|
IsAbstract |
False |
||||
|
References |
NodeClass |
BrowseName |
DataType |
TypeDefinition |
Other |
|
Subtype of ProcessAnalyserType defined in 7.3, i.e. inheriting the InstanceDeclarations of that Node |
|||||
|
0:HasComponent |
Object |
DeviceConditionSet |
|
0:BaseObjectType |
O |
|
0:HasDictionaryEntry |
Object |
|
0:IrdiDictionaryEntryType |
|
|
|
Conformance Units |
|||||
|
PA-DIM TocAnalyserType |
|||||
|
PA-DIM TocAnalyserType CarrierGasGaugePressure |
|||||
|
PA-DIM TocAnalyserType SampleWaterVolumeFlow |
|||||
|
PA-DIM TocAnalyserType ActualInjectedVolume |
|||||
3:0112/2///61987#ABP444#002 is a TOC analyser device specific manifestation of the 3:<DictionaryEntryName> placeholder described in PADIMType.
TocAnalyserType is defined by IRDI as ABP444#002 which states “sum parameter analyser for the determination of total organic carbon in water by oxidation”.
DeviceConditionSet is a container object for the condition parameters of the device. It is inherited from PADIMType and has an additional interface reference to ITocDeviceConditionSetType to add TOC analyser device specific condition variables.
The components of TocAnalyserType have additional references which are defined in Table 116.
Table 116 – TocAnalyserType additional References
|
SourceBrowsePath |
Reference Type |
Is Forward |
TargetBrowsePath |
|||
|
DeviceConditionSet |
0:HasInterface |
True |
ITocDeviceConditionSetType |
|||
|
0:HasDictionaryEntry |
True |
||||
|
0:HasDictionaryEntry |
True |
||||
|
0:HasDictionaryEntry |
True |
||||
|
0:HasDictionaryEntry |
True |
||||
|
0:HasDictionaryEntry |
True |
||||
|
0:HasDictionaryEntry |
True |
||||
|
0:HasDictionaryEntry |
True |
The components of TocAnalyserType have additional subcomponents which are defined in Table 117.
Table 117 – TocAnalyserType additional subcomponents
|
BrowsePath |
References |
NodeClass |
BrowseName |
DataType |
TypeDefinition |
Others |
|
DeviceConditionSet |
0:HasComponent |
Variable |
CarrierGasVolumeFlow |
0:Float |
0:AnalogUnitType |
O |
|
DeviceConditionSet |
0:HasComponent |
Variable |
CarrierGasGaugePressure |
0:Float |
0:AnalogUnitType |
O |
|
DeviceConditionSet |
0:HasComponent |
Variable |
ReactorTemperature |
0:Float |
0:AnalogUnitType |
O |
|
DeviceConditionSet |
0:HasComponent |
Variable |
SampleWaterVolumeFlow |
0:Float |
0:AnalogUnitType |
O |
|
DeviceConditionSet |
0:HasComponent |
Variable |
ReferenceInjectionVolume |
0:Float |
0:AnalogUnitType |
O |
|
DeviceConditionSet |
0:HasComponent |
Variable |
ActualInjectedVolume |
0:Float |
0:AnalogUnitType |
O |
|
DeviceConditionSet |
0:HasComponent |
Variable |
CoolerTemperature |
0:Float |
0:AnalogUnitType |
O |
The child Nodes of the TocAnalyserType have additional Attribute values defined in Table 118.
Table 118 – TocAnalyserType Attribute values for child Nodes
|
BrowsePath |
Value Attribute |
|||
|
0.0 |
|||
|
NamespaceUri: http://www.opcfoundation.org/UA/units/cdd/IEC62720UnitId: 705747637DisplayName: l/h Description: litre per hour |
|||
|
0.0 |
|||
|
NamespaceUri: http://www.opcfoundation.org/UA/units/cdd/IEC62720UnitId: 705749552DisplayName: mbar Description: millibar |
|||
|
0.0 |
|||
|
NamespaceUri: http://www.opcfoundation.org/UA/units/cdd/IEC62720UnitId: 705741427 DisplayName: °C Description: degree Celsius |
|||
|
0.0 |
|||
|
NamespaceUri: http://www.opcfoundation.org/UA/units/cdd/IEC62720UnitId: 705749685DisplayName: ml/min Description: millilitre per minute |
|||
|
0.0 |
|||
|
NamespaceUri: http://www.opcfoundation.org/UA/units/cdd/IEC62720 UnitId: 705749652DisplayName: ml Description: millilitre |
|||
|
0.0 |
|||
|
NamespaceUri: http://www.opcfoundation.org/UA/units/cdd/IEC62720 UnitId: 705749652DisplayName: ml Description: millilitre |
|||
|
0.0 |
|||
|
NamespaceUri: http://www.opcfoundation.org/UA/units/cdd/IEC62720UnitId: 705741427 DisplayName: °C Description: degree Celsius |