The IInfraredSignalConditionSetType provides the interface to Infrared signal specific condition variables and is formally defined in Table 103

Table 103 – IInfraredSignalConditionSetType definition

Attribute

Value

BrowseName

IInfraredSignalConditionSetType

IsAbstract

True

References

NodeClass

BrowseName

DataType

TypeDefinition

Other

Subtype of 0:BaseInterfaceType defined in OPC 10000-5, i.e. inheriting the InstanceDeclarations of that Node

0:HasComponent

Variable

SensingElementTemperature

0:Float

0:AnalogUnitType

O

0:HasProperty

Variable

SourceResidualLife

0:Float

0:PropertyType

O

0:HasProperty

Variable

TransmissionRatio

0:Float

0:PropertyType

O

0:HasProperty

Variable

SensorNextCalibrationFixed

0:Float

0:PropertyType

O

0:HasProperty

Variable

SensorNextCalibrationDynamic

0:Float

0:PropertyType

O

0:HasProperty

Variable

PowerOnDurationSensor

0: Duration

0:PropertyType

O

0:HasProperty

Variable

SensingElementResidualLife

0:Float

0:PropertyType

O

0:HasProperty

Variable

RelativeGasFlowRate

0:Float

0:PropertyType

O

0:HasProperty

Variable

SensingElementResidualSensitivity

0:Float

0:PropertyType

O

Conformance Units

PA-DIM InfraredSignalType

PA-DIM InfraredSignalType SourceResidualLife

PA-DIM InfraredSignalType TransmissionRatio

PA-DIM InfraredSignalType SensorNextCalibrationFixed

PA-DIM InfraredSignalType SensorNextCalibrationDynamic

PA-DIM InfraredSignalType PowerOnDurationSensor

PA-DIM InfraredSignalType SensingElementResidualLife

SensingElementTemperature is defined by IRDI as ABP565#001 which states "temperature measured at a sensing element".

SourceResidualLife is defined by IRDI as ABQ041#001 which states "degradation of an infrared radiation source expressed as a value between 1 (good) and 0 (bad)".

TransmissionRatio is defined by IRDI as ABP582#001 which states "ratio of the value of a specified radiation quantity in the centre of a beam of specified radiation quality and under specified geometrical conditions after passage through a material to the value which would be present at the same position without this material in the beam".

SensorNextCalibrationFixed is defined by IRDI as ABQ016#001 which states "time expressed in days that can elapse until the next calibration, calculated from the configured calibration interval".

SensorNextCalibrationDynamic is defined by IRDI as ABQ017#001 which states "time expressed in days that can elapse until the next calibration, estimated from operational or historical information".

PowerOnDurationSensor is defined by IRDI as ABQ010#001 which states "summed duration of time intervals for which the sensor was in an operating powered state".

SensingElementResidualLife is defined by IRDI as ABQ040#001 which states "degradation of a sensing element expressed as a value between 1 (good) and 0 (bad) calculated during its calibration".

RelativeGasFlowRate is defined by IRDI as ABQ011#001 which states "flow rate of gas expressed as a value between 100 (good) and 0 (bad)".

SensingElementResidualSensitivity is defined by IRDI as ABQ040#001 which states "degradation of a sensing element expressed as a value between 1 (good) and 0 (bad) calculated during its calibration".

The components of IInfraredSignalConditionSetType have additional references which are defined in Table 104.

Table 104 – IInfraredSignalConditionSetType additional References

SourceBrowsePath

Reference Type

Is Forward

TargetBrowsePath

SensingElementTemperature

0:HasDictionaryEntry

True

3:0112/2///61987#ABP565#001

SourceResidualLife

0:HasDictionaryEntry

True

3:0112/2///61987#ABQ041#001

TransmissionRatio

0:HasDictionaryEntry

True

3:0112/2///61987#ABP582#001

SensorNextCalibrationFixed

0:HasDictionaryEntry

True

3:0112/2///61987#ABQ016#001

SensorNextCalibrationDynamic

0:HasDictionaryEntry

True

3:0112/2///61987#ABQ017#001

PowerOnDurationSensor

0:HasDictionaryEntry

True

3:0112/2///61987#ABQ010#001

SensingElementResidualLife

0:HasDictionaryEntry

True

3:0112/2///61987#ABP584#001

RelativeGasFlowRate

0:HasDictionaryEntry

True

3:0112/2///61987#ABQ011#001

SensingElementResidualSensitivity

0:HasDictionaryEntry

True

3:0112/2///61987#ABQ040#001

The child Nodes of the IInfraredSignalConditionSetType have additional Attribute values defined in Table 105.

Table 105 IInfraredSignalConditionSetType Attribute values for child Nodes

BrowsePath

Value Attribute

SensingElementTemperature

0

SourceResidualLife

1.0

TransmissionRatio

0

SensorNextCalibrationFixed

0

SensorNextCalibrationDynamic

0

PowerOnDurationSensor

0

SensingElementResidualLife

1.0

RelativeGasFlowRate

0

SensingElementResidualSensitivity

1.0