The IZirconiumDioxideSignalConditionSetType provides the interface to Zirconium dioxide measurement signal specific condition variables and is formally defined in Table 73.
Table 73 – IZirconiumDioxideSignalConditionSetType definition
|
Attribute |
Value |
||||
|
BrowseName |
IZirconiumDioxideSignalConditionSetType |
||||
|
IsAbstract |
True |
||||
|
References |
NodeClass |
BrowseName |
DataType |
TypeDefinition |
Other |
|
Subtype of 0:BaseInterfaceType defined in OPC 10000-5, i.e. inheriting the InstanceDeclarations of that Node |
|||||
|
0:HasComponent |
Variable |
RelativeHeatOutput |
0:Float |
0:AnalogUnitType |
O |
|
0:HasComponent |
Variable |
CellResistance |
0:Float |
0:AnalogUnitType |
O |
|
0:HasProperty |
Variable |
SensingElementResidualLife |
0:Float |
0:PropertyType |
O |
|
0:HasComponent |
Variable |
SensingElementTemperature |
0:Float |
0:AnalogUnitType |
O |
|
0:HasComponent |
Variable |
SampleGasVolumeFlow |
0:Float |
0:AnalogUnitType |
O |
|
Conformance Units |
|||||
|
PA-DIM ZirconiumDioxideSignalType |
|||||
|
PA-DIM ZirconiumDioxideSignalType RelativeHeatOutput |
|||||
|
PA-DIM ZirconiumDioxideSignalType CellResistance |
|||||
|
PA-DIM ZirconiumDioxideSignalType SensingElementResidualLife |
|||||
|
PA-DIM ZirconiumDioxideSignalType SampleGasVolumeFlow |
|||||
RelativeHeatOutput is defined by IRDI as ABP585#001 which states “relative heat output referred to the maximum heat output to keep the sensor at its setpoint temperature during operation”.
SensingElementResidualLife is defined by IRDI as ABP584#001 which states "degradation of a sensing element expressed as a value between 1 (good) and 0 (bad)".
SensingElementTemperature is defined by IRDI as ABP565#001 which states “temperature measured at a sensing element”.
SampleGasVolumeFlow is defined by IRDI as ABP562#001 which states “volume flow of a sample gas through a detection system”.
The components of IZirconiumDioxideSignalConditionSetType have additional references which are defined in Table 74.
Table 74 – IZirconiumDioxideSignalConditionSetType additional References
|
SourceBrowsePath |
Reference Type |
Is Forward |
TargetBrowsePath |
||
|
RelativeHeatOutput |
0:HasDictionaryEntry |
True |
|||
|
0:HasDictionaryEntry |
True |
|||
|
CellResistance |
0:HasDictionaryEntry |
True |
|||
|
SensingElementResidualLife |
0:HasDictionaryEntry |
True |
|||
|
SensingElementTemperature |
0:HasDictionaryEntry |
True |
|||
|
0:HasDictionaryEntry |
True |
|||
|
SampleGasVolumeFlow |
0:HasDictionaryEntry |
True |
|||
|
0:HasDictionaryEntry |
True |
The child Nodes of the IZirconiumDioxideSignalConditionSetType have additional Attribute values defined in Table 75.
Table 75 – IZirconiumDioxideSignalConditionSetType Attribute values for child Nodes
|
BrowsePath |
Value Attribute |
||
|
RelativeHeatOutput |
0.0 |
||
|
NamespaceUri: http://www.opcfoundation.org/UA/units/cdd/IEC62720 UnitId: 705741328 DisplayName: % Description: percent |
||
|
CellResistance |
0.0 |
||
|
SensingElementResidualLife |
1.0 |
||
|
SensingElementTemperature |
0.0 |
||
|
NamespaceUri: http://www.opcfoundation.org/UA/units/cdd/IEC62720UnitId: 705741427 DisplayName: °CDescription: degree Celsius |
||
|
SampleGasVolumeFlow |
0.0 |
||
|
NamespaceUri: http://www.opcfoundation.org/UA/units/cdd/IEC62720UnitId: 705747637DisplayName: l/hDescription: litre per hour |