7.6.10 ControllerParameterType ObjectType Definition

The ControllerParameterType represents a pair of target and current value variables for a specific mode of the MultiModeAnalogControlFunction (which typically have the same engineering unit).

Table 107 – ControllerParameterType Definition

Attribute

Value

BrowseName

ControllerParameterType

IsAbstract

False

References

Node Class

BrowseName

DataType

TypeDefinition

Other

Subtype of the BaseObjectType defined in OPC 10000-5

0:HasComponent

Object

AlarmMonitor

0:ExclusiveDeviationAlarmType

O

0:HasComponent

Variable

CurrentValue

0:Double

0:AnalogUnitRangeType

M, R

0:HasComponent

Variable

TargetValue

0:Double

0:AnalogUnitRangeType

M, RW

Conformance Units

LADS ControllerParameterType

AlarmMonitor indicates whether the deviation from a setpoint exceeds the limit. See: 10000-9: Alarms & Conditions | ExclusiveDeviationAlarmType.

CurrentValue is the current process value.

TargetValue is the targeted set-point value.