This Method ends the current Energy Saving Mode.

Signature

EndPause (

[out] 0:DurationCurrentTimeToOperate

[out] 0:ByteReturnCode

);

Argument

Description

CurrentTimeToOperate

Time needed to reach “Ready to operate” if successful, 0.

ReturnCode

Return code.

The Method Result Codes (defined in Call Service) are defined in Table 33.

ReturnCodes are defined in Table 34.

Table 33 shows the possible values for the Method call result codes.

Table 33 – Possible Method result codes

Result Code

Description

Good

The Method execution was successful and the ReturnCode parameter has the value 0x00 (”Success”).

Uncertain

The Method execution was successful, but the ReturnCode parameter indicates an error.

Bad_UserAccessDenied

The user has not the right to execute the Method. The client shall not evaluate the ReturnCode parameter.

Bad_UnexpectedError

The server is not able to execute the function because an unexpected error occurred. The device might be temporarily unavailable or unreachable due to network failure. The client shall not evaluate the ReturnCode parameter.

Table 34 shows the possible values for the out parameter ReturnCode.

Table 34 – Possible ReturnCode parameter Values

ReturnCode

Description

0x00

Success.

0x50

No suitable energy-saving mode available.

0x52

No switch to requested energy-saving mode because of invalid mode ID.

0x53

No switch to Energy Saving Mode because of state operate.

0x54

Service or function not available due to internal device status.