Errata exists for this version of the document.

Table 56 describes the details of the A & C Non-Exclusive Alarming Server Facet. This Facet requires support for Alarms with multiple sub-states that identify different limit Conditions. This Facet builds upon the A&C Alarm Server Facet. The term non-exclusive means more than one sub-state can be active at a time. For example, if a temperature exceeds the HighHigh limit the associated non-exclusive LevelAlarm will be in both the High and the HighHigh sub-state. This Facet requires that a server support at least one of the optional alarm models: Limit, RateOfChange or Deviation.

Table 56 – A & C Non-Exclusive Alarming Server Facet

Group

Conformance Unit / Profile Title

Optional

Profile

A & C Alarm Server Facet

False

Alarms and Conditions

A & C Non-Exclusive Deviation

True

Alarms and Conditions

A & C Non-Exclusive Level

True

Alarms and Conditions

A & C Non-Exclusive Limit

False

Alarms and Conditions

A & C Non-Exclusive RateOfChange

True