Errata exists for this version of the document.
Table 56 describes the details of the A & C Non-Exclusive Alarming Server Facet. This Facet requires support for Alarms with multiple sub-states that identify different limit Conditions. This Facet builds upon the A&C Alarm Server Facet. The term non-exclusive means more than one sub-state can be active at a time. For example, if a temperature exceeds the HighHigh limit the associated non-exclusive LevelAlarm will be in both the High and the HighHigh sub-state. This Facet requires that a server support at least one of the optional alarm models: Limit, RateOfChange or Deviation.
Table 56 – A & C Non-Exclusive Alarming Server Facet
Group |
Conformance Unit / Profile Title |
Optional |
False |
||
Alarms and Conditions |
A & C Non-Exclusive Deviation |
True |
Alarms and Conditions |
A & C Non-Exclusive Level |
True |
Alarms and Conditions |
A & C Non-Exclusive Limit |
False |
Alarms and Conditions |
A & C Non-Exclusive RateOfChange |
True |