6.6.32 A & C Acknowledgeable Alarm Server Facet

Table 54 describes the details of the A & C Acknowledgeable Alarm Server Facet. This Facet requires support for Acknowledgement of active Alarms. This Facet builds upon the A & C Alarm Server Facet. Acknowledgement requires support of the Acknowledge Method and the Acknowledged state. Support of the Confirmed state and the Confirm Method is optional.

Table 54 – A & C Acknowledgeable Alarm Server Facet

Group

Conformance Unit / Profile Title

Optional

Profile

A & C Alarm Server Facet

False

Alarms and Conditions

A & C Acknowledge

False

Alarms and Conditions

A & C Confirm

True