This OPC UA ObjectType represents the BACnet double out of Range event algorithm.

The BACnetDoubleOutOfRangeAlgorithmType is formally defined in Table 64.

Table 64 – BACnetDoubleOutOfRangeAlgorithmType Definition

Attribute

Value

BrowseName

BACnetDoubleOutOfRangeAlgorithmType

IsAbstract

False

References

NodeClass

BrowseName

DataType

TypeDefinition

Other

Subtype of the BACnetEventAlgorithmType defined in 8.9.

0:HasProperty

Variable

HighLimit

0:Double

0:PropertyType

M

0:HasProperty

Variable

LowLimit

0:Double

0:PropertyType

M

0:HasProperty

Variable

Deadband

0:Double

0:PropertyType

M

0:HasProperty

Variable

LimitEnable

BACnetLimitEnable

0:PropertyType

M

The BACnetDoubleOutOfRangeAlgorithmType ObjectType is a concrete type and can be used directly.

This OPC UA Property, of DataType Double, is the HighLimit parameter for the object’s event algorithm.

The HighLimit value represents the upper limit of the range considered normal.

This OPC UA Property, of DataType Double, is the LowLimit parameter for the object’s event algorithm.

The LowLimit value represents the lower limit of the range considered normal.

This OPC UA Property, of DataType Double, is the Deadband parameter for the object’s event algorithm.

The Deadband variable value represents the deadband that is applied to the limit before a return to Normal event state is indicated.

This OPC UA Property, of DataType BACnetLimitEnable, shall indicate three separate flags that enable and disable the delivery of TO_OFFNORMAL, TO_FAULT, and TO_NORMAL notifications. The DataType BACnetLimitEnable is defined in 10.3.4.