9 Profiles and ConformanceUnits ToC Previous Next

9.1 Conformance Units ToC Previous Next

This chapter defines the corresponding Conformance Units for the OPC UA Information Model for Pumps and Vacuum Pumps.

Table 152 – Conformance Units for OPC UA for Pumps and Vacuum Pumps

Category Title Description
Server Base System The PumpType is implemented by the server.
Server Historizing The Historizing Attribute and the HistoryRead Attribute is True for at least one Quantity.
Server Limit Alarm Status The ObjectTypes MeasurementsType, DriveMeasurementsType, InletConnectionMeasurementsType and OutletConnectionMeasurementsType have a 0:GeneratesEvent reference targeting one of the subtypes of the 0:LimitAlarmType.
Server PumpClass Data The PumpClass Property of the Design FunctionalGroup is instantiated for all instantiated Pumps and carries a legal value.
Server Pump Connection Port At least one of the InletConnectionPortType or the OutletConnectionPortType is implemented by the Server.
Server Pump Control At least one of ControlType, ActuationType or one of subtypes of ActuationType is implemented by the Server.
Server Pump Drive Port The DrivePortType is implemented by the server.
Server Pump Identification Supports the PumpIdentificationType with all its mandatory
InstanceDeclarations, and optionally the optional InstanceDeclarations with read access.
Server Pump PumpType Mandatory Nodes All nodes declared as mandatory in the PumpType are available in the AdressSpace.
Server Supervision Health Status Every instance of a variable of type 0:TwoStateDiscreteType in the subtypes of SupervisionType has a GeneratesEvent reference targeting one of the subtypes of the 2:DeviceHealthDiagnosticAlarmType.

Previous Next