6 Profiles

6.6 Profile tables

6.6.34 A & C Non-Exclusive Alarming Server Facet

Table 56 describes the details of the A & C Non-Exclusive Alarming Server Facet. This Facet requires support for Alarms with multiple sub-states that identify different limit Conditions. This Facet builds upon the A&C Alarm Server Facet. The term non-exclusive means more than one sub-state can be active at a time. For example, if a temperature exceeds the HighHigh limit the associated non-exclusive LevelAlarm will be in both the High and the HighHigh sub-state. This Facet requires that a server support at least one of the optional alarm models: Limit, RateOfChange or Deviation.
Table 56 – A & C Non-Exclusive Alarming Server Facet
Group | Conformance Unit / Profile Title | Optional |
---|---|---|
Profile | A & C Alarm Server Facet | False |
Alarms and Conditions | A & C Non-Exclusive Deviation | True |
Alarms and Conditions | A & C Non-Exclusive Level | True |
Alarms and Conditions | A & C Non-Exclusive Limit | False |
Alarms and Conditions | A & C Non-Exclusive RateOfChange | True |