This OPC UA ObjectType represents the BACnet object type Analog Value. This is a control system parameter that resides in the memory of the BACnet Device.

Figure 16 shows an overview for the BACnetAnalogValueType with its Properties and related ObjectTypes. It is formally defined in Table 16.

image022.png

Figure 16 BACnetAnalogValueType overview

The BACnetAnalogValueType ObjectType is formally defined in Table 16.

Table 16 BACnetAnalogValueType Definition

Attribute

Value

BrowseName

BACnetAnalogValueType

IsAbstract

False

References

NodeClass

BrowseName

DataType

TypeDefinition

Other

Subtype of the BACnetAnalogType

0:HasProperty

Variable

Priority_Array

BACnetPriorityValue [16]

0:PropertyType

O

0:HasProperty

Variable

Relinquish_Default

0:Float

0:PropertyType

O

The BACnetAnalogValueType ObjectType is a concrete type and can be used directly.

This OPC UA Property, of DataType BACnetPriorityValue [16], represents the BACnet property Priority_Array. The BACnetPriorityValue DataType is defined in 10.6.4.

It is an array that contains prioritized commands that are in effect for this object. See 3.2.1 for details on command prioritization.

This OPC UA Property, of DataType 0:Float, represents the BACnet property Relinquish_Default.

It is the default value to be used for the Present_Value when all command priority values in the Priority_Array have a NULL value. See 3.2.1 for details on command prioritization.